Page: 30
FM-200® OPERATION, DESIGN, & SERVICE MANUAL
Revision F
Document # DOC102
Issued: February 1, 2009
Revised: 11-Nov-2011
40YE
Section 2 System Description and Components
Primary
Cylinder
Slave
Cylinder
Slave
Cylinder
TO ZONE 1
DISCHARGE
NOZZLES
TO ZONE 2
DISCHARGE
NOZZLES
Selector Valve
(LARGEST
VALVE MUST BE
PLACED FIRST)
Selector Valve
(SMALLEST
VALVE MUST BE
PLACED LAST)
Lockout Valve
w/ Limit Switch
Optional
Regulator
(P/N 19170)
Discharge
Relief Valve
450 psi
(P/N 19317)
Discharge
Relief Valve
125 psi
(P/N 19316)
Discharge
Relief Valve
450 psi
(P/N 19317)
Required
when Optional
Lockout Valve
Installed
Discharge
Pressure
Switch
(P/N 18773)
Figure 2.5b Selector Valve Arrangement - TYPE B
NOTE: The cylinder manifold used in
selector valve system must be an end-feed
or side-feed type manifold connected to the
selector valve manifold.
Minimum distance of 10 pipe
diameters between center points
of last cylinder outlet and rst
selector valve
SELECTOR VALVE MANIFOLD
CYLINDER MANIFOLD
• TYPE B - e Type B arrangement consists of a selector valve manifold located downstream of an
end-feed cylinder manifold. is arrangement requires pipe modeling and for a selector valve manifold
calculation to be performed. Manifold must be designed and installed in accordance with the calculations
determined using the Janus Design Suite® ow calculation software and the limitations detailed in the
Janus Design Suite® FM-200 Flow Calculation Manual (DOC106). Refer to Figure 2.5b.