EasyManua.ls Logo

Janus FM-200 Sv Series - Page 75

Default Icon
131 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page: 61
FM-200® OPERATION, DESIGN, & SERVICE MANUAL
Revision F
Document # DOC102
Issued: February 1, 2009
Revised: 11-Nov-2011
40YE
Section 4 System Installation
Figure 4.1.6.2 Alternate Pilot Actuation Line Conguration – Utilizing Copper Tubing
(Mv Series Shown. Same for all Series)
Figure 4.1.6.3 Alternate Pilot Actuation Line Conguration – Utilizing Schedule 40 Pipe
(Mv Series Shown. Same for all Series)
Vent Check
(P/N 10173)
Vent Check
(P/N 10173)
10” (254 mm)
Suggested
Height
1/4” (8 mm)
NPT Pipe Plug
(Provided By
Installer)
1/4” (8 mm) Male
45°SAE Flared x
Male NPT
Adapter Nipple
(Provided By
Installer)
1/4” (8 mm) Male 45°SAE
Flared x Male NPT Tee
(Provided By Installer)
Pilot Actuation
End Line Tee
(P/N 18611)
1/4” (8 mm) O.D.
Copper Tubing
(Provided By Installer)
1/4” (8 mm)
Schedule 40 Pipe
(Provided By Installer)
NPT Style Pilot
Actuation Check Valve
(P/N 10262)
Pilot Actuation Check
Valve
(P/N 18560)
1/4” (8 mm) Female
NPT x Male 45° SAE
Flared Adapter
(Provided By Installer)
Pilot Actuation Adapter
(P/N 18624)
Sv Series Only
Pilot Actuation Adapter
(P/N 18624)
Sv Series Only
NPT Pilot Actuation Check
Valve Adapter Hex Nipple
(Sv Series: P/N 18713)
(Mv and Lv Series: P/N 19192)
Primary
Cylinder
Primary
Cylinder
Slave
Cylinder
Slave
Cylinder
Slave
Cylinder
Slave
Cylinder
Slave
Cylinder
Slave
Cylinder
Slave
Cylinder
Slave
Cylinder
24” Flex Hose
(610 mm)
(P/N 18649)
24” Flex Hose
(610 mm)
(P/N 18649)
Male NPT
Adapter
(P/N 18625)
Male NPT
Adapter
(P/N 18625)
1/4” (8 mm) Female
NPT x Female NPT Tee
(Provided By Installer)

Table of Contents