54
Figure 7-2 Inverter start to operation inverter
Note
If there is no water output , or flow rate is less than normal situation, even
there has abnormal sound of pump, possible reasons are shown below:
a) Pump motor reversal caused by wrong phase sequence connection. Stop
inverter, enter into M-Mode setting interface, please refer to8.3.2.2 DSP
parameter setting ;
b) Output power of PV array is not enough.
If there occurs abnormal during the first commission, please refer to 9.1
Troubleshooting for trouble shooting.
If it occurs output frequency is very low, and output current is very big at the
same time, please refer to 7.4.2.2 Motor parameters setting by manual.