Table 7: CGM09090 and CGE09090 UI Inputs and jumper
labels
Universal Input
label
Jumper label on circuit board
UI-1 J13
UI-2 J14
UI-3 J15
UI-4 J16
UI-5 J17
UI-6 J18
UI-7 J19
Table 8: CGM04060 and CGE04060 UI Inputs and jumper
labels
Universal Input
label
Jumper label on circuit board
UI-1 J10
UI-2 J11
UI-3 J12
Setting up a local display
CGM09090-0H and CGE09090-0H models have an integral
color display and navigation keypad that can be set up to
enable local monitoring of the equipment controller's I/O
points and parameters/setpoints, including any I/O points
of the expansion modules connected on the SA Bus.
CGM/CGE models that do not have an integral display can
be connected to an F4-DLK0350 local controller display
or an FX-DIS1710 local controller display. If the display
is configured with a local password, the equipment
controller and display must be running compatible
firmware versions. If the display is not configured
with a local password, it is compatible with equipment
controllers at any firmware revision. See the following
table for further details:
Note: Do not downgrade CGM or CGE models with
integral displays to firmware version 9.0 or earlier.
Use only firmware version 10.0 or later with CGM or
CGE models with integral displays.
Table 9: Equipment Controller and display
compatibility for displays configured with a local
password
Display model
and firmware
version
Controller
running 10.x
firmware or
greater
Controller
running 9.x
firmware or
earlier
DLK0350 running
10.x firmware or
greater
Compatible Not compatible
DLK0350 running
9.x firmware
Not compatible Compatible
DIS1710 running
6.2 firmware
Not compatible Compatible
The DLK0350 and DIS1710 models should not be
connected to CGM/CGE -0H models that include an
integral display.
For detailed information about setting up and operating
a remotely connected DLK0350 display, refer to the Local
Controller Display User Guide (LIT-12013762). For detailed
information about setting up and operating a remotely
connected FX-DIS1710 display, refer to the FX-DIS Local
Controller Display Technical Bulletin (LIT-12011666).
Input/Output wiring validation
The CGM/CGE controllers ship with a default state that
can assist in validating the wiring of the input and output
terminals prior to download of an application file. When
the controller is powered on in this state, the Fault LED
will flash in a pattern of two quick blinks and then a long
pause (see LED status and states).
To make use of this feature, ensure the rotary switches
are set to the desired address or controller number and
wire the input and output terminals. Apply power to the
controller and connect to the device with either a MAP
Gateway, F4-DLK0350 local controller display, or a FX-
DIS1710 local display to view the points in the controller.
The controller will report an Operational status even
though there is no true application loaded. CCT will not be
able to commission or upload the device as a result until
a true application is downloaded. The application name
displayed will be the address of the controller followed by
the model of the controller and “Default State”.
For example, a CGM09090 controller whose rotary
switches are set to 8 would have the default state
application name of “8-CGM09090 Default State”.
The default state creates I/O points for all connections
on the input and output terminals. It assumes all
Universal Inputs (UIs) are Nickel temperature sensors. All
Configurable Outputs (COs) are treated as Binary Outputs
(BOs) with an initial value of 0. The default state also takes
input from a Network Sensor at address 199. If there is
no connected Network Sensor, the startup of this default
state will be delayed by 30 seconds as the controller
attempts to establish connection with the sensor.
Commissioning the controller
You commission equipment controllers with the CCT
software using Mobile Access Portal (MAP) Gateway or in
BACnet router mode when connected to an FX supervisory
controller. For detailed information about commissioning
the controller using MAP, refer to Mobile Access Portal
Gateway User Guide (LIT-12011999) or Controller Tool Help
(LIT-12011147).
Commission controllers using the following connection
types.
Connection
Type
CGM CGE
MAP 4.2+/
BACnet Router
X X
Direct Ethernet X
Supervisor
Passthru
X X
F4-CG Series General Purpose Application Controllers Installation Guide 21