EasyManuals Logo

Johnson Controls IFC-1010 Wiring Manual

Johnson Controls IFC-1010
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #66 background imageLoading...
Page #66 background image
66 Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009
Appendix D: Canadian Versions of SLC Devices
Note: Only FlashScan/CLIP devices are listed for releasing applications.
UL-listed SLC Device ULC-listed SLC Device
2951TMJ (Acclimate™) 2951TMJA Intelligent detector that combines a photoelectric sensing
chamber and fixed temperature heat detection
(135°F/57.2°C). FlashScan capable.
FSB-200, FSB-200S FSB-200A, FSB-200SA Addressable, intelligent, single-ended beam smoke detector
with built-in sensitivity testing. FlashScan and CLIP mode.
1951J 1951JA Addressable, intelligent smoke detector that incorporates an
ionization sensing chamber. Designed to provide open area
protection. FlashScan capable.
2951J 2951JA Analog, addressable intelligent smoke detector that uses a
photoelectric sensing chamber. Listed for use in ducts.
Designed to provide open area protection. FlashScan
capable.
2951TJ 2951TJA Adds thermal sensors that will alarm at a fixed temperature
of 135°F (57°C).
5951J 5951JA Intelligent thermistor sensing circuit for fast response.
Designed to provide open area protection with 50 foot
spacing capability. A fixed temperature sensor with 135°F
fixed temperature alarm. FlashScan capable.
5951RJ 5951RJA Incorporates a thermal rate of rise of 15°F (9.4°C).
FlashScan capable.
5951HJ High temperature sensor with 190°F (87.8°C) fixed
temperature alarm.
DH300PL
DH300PLA
Photoelectric Duct Detector, Low-flow
DH300RPL DH300RPLA Photoelectric Duct Detector, Low-flow
FTX-P1J Smoke detector that provides early warning smoke
detection in hostile environments where traditional smoke
detectors are not practical. Discontinued.
FTX-P2J FTX-P2JA Smoke detector provides early warning smoke detection in
hostile environments where traditional smoke detectors are
not practical.
7251J Early detection laser detector, similar to the 7351J, but
limited to CLIP mode operation only. Discontinued.
7351JLow Profile Laser
Detector
7351JA An advanced intelligent photoelectric detector that uses a
laser diode, special optics, and signal processing to obtain
extremely high sensitivity.
Bases
B210LPJ B210LPJA Standard U.S. Low-Profile base (6", 15.24 cm)
B501J B501JA Standard European flangeless base (4", 10.16 cm)
B501BH, B501BHT B501BHA, B501BHTA Sounder base, includesB501J Sounder base with temporal
sounder (UL 8th Edition)
B501BH-2, B501BHT-2 B501BH-2A, B501BHT-2A Sounder base, includesB501J Sounder base with temporal
sounder (UL 9th Edition)
B224RB
B224RBA
Low Profile Intelligent relay base
B510B-FTXJ B510B-FTXJA Base for a hostile environment detector.
Monitor and Zone Interface Modules
M300MJ
M300MJA
Used for normally open contact alarm initiating devices,
such as manual pull stations, four-wire smoke detectors,
heat detectors, waterflow, and supervisory devices
M302MJ M302MJA Used to interface with two-wire smoke detectors in addition
to normally open contacts

Table of Contents

Other manuals for Johnson Controls IFC-1010

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls IFC-1010 and is the answer not in the manual?

Johnson Controls IFC-1010 Specifications

General IconGeneral
BrandJohnson Controls
ModelIFC-1010
CategoryControl Panel
LanguageEnglish

Related product manuals