EasyManua.ls Logo

Johnson Controls IFC-2020 - Page 73

Johnson Controls IFC-2020
136 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Hardware Installation—Installing the IFC-1010/2020
73
lib200
Figure 47: LIB-200
The LIB-200A field wiring is electrically isolated from the rest of the
system so that any two ground faults on separate SLCs will not cause
invalid replays from devices. A short to any other system circuit will not
cause communication loss. The LIB-200A has an earth fault detection
circuit with selectable high/low sensitivity and disable. The LIB-200A
supports up to 12,500 feet of field wiring on Ports A and B for Style 4 and
12,500 feet total for Style 6 and 7. The maximum loop resistance for style
4 is 50 ohms on Ports A and B and 50 ohms total for Styles 6 and 7. The
LIB-200A has two LEDs; yellow displays earth fault trouble and red
indicates initiated alarm condition during local mode only (refer to
Figure 48).
The LIB-400 filed wiring is electrically isolated from the rest of the system
so that any two ground faults on separate SLCs will not cause invalid
replays from devices. A short on to any other system circuit will not cause
communication loss. The LIB-400 has an earth fault has an earth fault
detection circuit with selectable high/low sensitivity and disable.
The LIB-400 supports up to 12,500 feet of field wiring on Ports A and B
for Style 4 and 12,500 for Style 6 and 7. The maximum loop resistance for
Style 4 is 50 ohms on Ports A and B and 50 ohms total for Styles 6 and 7.
The LIB-400 supports the Local Mode General Alarm Bus, a feature that
permits limited alarm function in the unlikely event of a CPU failure. The
LIB-400 has two LEDs per loop; yellow indicates an earth fault and red
indicates an alarm condition during local mode only (refer to Figure 48).
LIB-200A
LIB-400

Table of Contents

Other manuals for Johnson Controls IFC-2020

Related product manuals