Hardware Installation—Installing the IFC-1010/2020
9
Introduction
The product that this document supports is UL (Underwriters
Laboratories) Multiple Listed, which requires that the content of the
documentation inherited from the manufacturer remain intact. Minor
changes clarify information such as vendor-specific product names and
literature names and numbers. More significant changes to the original
technical content, such as additions or corrections, are identified with
Note Numbers
Nx
. For the Note Number content, refer to the Application
and Clarification Notes section at the end of this document.
This document may contain references to some features that are not
supported before Metasys® Release 9.01. If you are using earlier firmware
releases, please ignore references to the following products:
•
NAM-232
•
LIB-200A
•
LIB-400
•
SIB-2048A
Also, the AVPS-24 and AVPS-24E have been replaced by the APS-6R.
The IFC-1010/2020 is an Intelligent Analog Addressable Combination
Fire Alarm/Security Control Panel capable of supporting the following:
Photoelectric, ionization, and thermal (heat) detectors.
Pull Stations and modules that monitor any conventional normally open
contact type devices (four wire smoke detectors, heat detectors, pull
stations, supervisory switches, water flow switches) or any normally
closed contact type device, such as a door contact that may be used in
security applications.
Modules that can supervise and switch power to notification appliances or
serve as Form-C control relays.
Notification appliance power is provided by the main power supply.
Additional notification appliance power may be provided by optional