Operating Limitations
TABLE 4 - OPERATING LIMITATIONS — LSWU025-LSWU105
MINIMUM MAXIMUM
Entering Air DX Coil-Dry Bulb 75.0°F 85.0°F
Entering Air DX Coil-Wet Bulb 62.0°F 72.0°F
Condenser Water Flow 2.5 GPM/Ton 3.0 GPM/Ton
Entering Cond. Water Temp with Economizer 40.0°F 90.0°F
Entering Cond. Water Temp with Condenser
Water Control Valve
40.0°F 90.0°F
Entering Cond. Water Temp w/o Condenser
Water Control Valve
60.0°F 90.0°F
Steam Heat-Steam Pressure 5 psig 15 psig
Hot Water Heat Entering Water Temp 140.0°F 160.0°F