FORM 145.05-EG2 (618)
58
JOHNSON CONTROLS
Air Pressure Drops (Cont’d)
LSWU025 Air Pressure Drops Across Clean Filters
0.000
0.050
0.100
0.150
0.200
0.250
0.300
6,000 6,500 7,0007,500 8,000 8,5009,000 9,50010,00010,500
4" (MERV8)
4" +4"(MERV 13 +
MERV 8)
Air Pressure Drop (inch w.c.)
LSWU032 Air Pressure Drops Across Clean Filters
0.000
0.050
0.100
0.150
0.200
0.250
0.300
0.350
0.400
0.450
7,0008,000 9,00010,00011,00012,00013,00014,000
4" (MERV8)
4" +4"(MERV 13 +
MERV 8)
Air Pressure Drop (inch w.c.)