T-4000 Product Bulletin 5
Thermostat Specification and Selection Guide (table rows continued from facing page)
Air Connections** Dial
Ranges
Special Features Code No. Suffix Shipping
Weight lb.***
T-4002 Two
Supply and Output
55 to 85° F Volume Amplifier,
Pneumatic Feedback
T-4002- ActionVert. Horiz
DIR 201 203
REV 202 204
0.4
T-4003 Three
Supply, Output,
and Remote Reset
Input
55 to 85° F Volume Amplifier,
Remote Readjustment--
from .15 to 2.5°F/PSI
(1.8 to 30°C/kPa)
T-4003- Horiz
DIR,DR 201 Horiz.
REV,RR 203 Mtg.
0.4
T-4054 Two
Supply and Output
Two dials
55 to 85° F
Energy Manager,
Pneumatic Feedback,
Adjustable Deadband--
between 5 and 12 PSIG
(35 and 84 kPa)
T-4054- Horiz or Vert.
DIR 1
REV 2
0.4
T-4100 One
Restricted
Supply/Output
55 to 85°F or
13 to 29°F
Pneumatic Feedback,
°F and °C Thermometer
T-4100-
(Vert. Mtg.)
F° Dial C° Dial
DIR 1 3
REV 2 4
0.2
T-4110 Two
Control and
Aspirator
66 to 82°F
(19 to 28°C)
Ball Control Port ,
Flexible Setpoint, Lever,
Adjustable Sensitivity
T-4110- w/o aspirator w/aspirator
DIR 1 2
REV 3 4
0.2
T-4506 Two
Supply and Output
Two dials
55 to 85°F
Volume Amplifier,
Pneumatic Feedback,
Manual Indexing Switch
(optional),
Element Identification
Labels
T-4506- mtg. w/switch w/o switch
DIR Horiz. 201 203
Vert. 202 204
REV Horiz. 209 217
0.4
T-4516 Three
Supply, Output,
and Switchline
Two dials
55 to 85°F
Volume Amplifier,
Pneumatic Feedback,
Manual Indexing Switch
(standard),
Element Identification
Labels
T-4516- DIR Horiz. 201
Vet. 202
0.4
T-4600 Two-Restricted
Supply/Output for
Heating and
Cooling
50 to 80°F
and 63 to
93°F or
10 to 27°C
and
17 to 34°C
Energy Manager,
Individual Adjustments
for Heating and Cooling,
Element Identification
Labels
T-4600-
(Vert. Mtg.)
Action F° Dial C° Dial
DIR 1 3
REV 2 4
DIR and REV 5 6
0.3
T-4756 Two
Supply and Output
Two dials
55 to 85°F
Volume Amplifier,
Models Available with
Factory Stops and
WARM-COOL dials,
Element Identification
Labels
T-4756- Action Mtg. F° Dial W-C Dial
DIR Horiz. 201 216
@15 PSIG Vert. 202
DIR Horiz. 205 217
@20 PSIG Vert. 206
0.4
Elements Single or Dual Bimetal Strips
*Supply Pressure Air Supply Must Be Clean, Dry, and Oil Free
**Air Connections Barbed Fittings for 5/32 in. O.D. Polytubing
Ambient Operating Temp Limits -20 to 130°F (-29 to 54°C)
Ambient Storage Temp Limits -20 to 150°F (-29 to 66°C) or -20 to 130°F for Units with Thermometers
***lb x 0.454 = kg
The performance specifications are nominal and conform to acceptable industry standards. For application at
conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall
not be liable for damages resulting from misapplication or misuse of its products.