TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions12
Floating Motor Timing (TEC2627-2 Model)
3
MSV 36 1 = 0.5 Minutes
2=1.0Minute
3=1.5Minutes
4=2.0Minutes
5=2.5Minutes
6=3.0Minutes
7=3.5Minutes
8=4.0Minutes
9=4.5Minutes
10 = 5.0 Minutes
11 = 5.5 Minutes
12 = 6.0 Minutes
13 = 6.5 Minutes
14 = 7.0 Minutes
15 = 7.5 Minutes
16 = 8.0 Minutes
17 = 8.5 Minutes
18 = 9.0 Minutes
On/Off Control CPH (TEC2627-2 Model)
3
MSV 37 1 = 3 CPH
2=4CPH
3=5CPH
4=6CPH
5=7CPH
6=8CPH
Direct/Reverse Acting (TEC2647-2 Model)
3
BV 38 0 = Direct Acting
1 = Reverse Acting
TEC26x7-aaa
8, 9
Device 72aaa N/A
1. This MS/TP Bus object is readable and only writable if the corresponding override object is set. (For example, Room Temp
has a corresponding override object of Room Temp Override. This corresponding override object needs to be set to
1=Override to be able to write Room Temp to a different value.)
2. This MS/TP Bus object may automatically release after 10 minutes with no BACnet traffic.
3. This MS/TP Bus object is readable and writable.
4. This MS/TP Bus object is valid only if it is written via the network.
5. This MS/TP Bus object is readable only.
6. The BI object type status is available even if the configuration is set to None.
7. If one setpoint of a pair of heating and cooling setpoints (for example, Occupied Heat Setpoint and Occupied Cool
Setpoint) is overridden, the other setpoint of the pair may be automatically adjusted by the thermostat to maintain the
minimum deadband between the two setpoints.
8. The designation aaa is the address of the device (from 004 to 127) on the MS/TP network.
9. Max_Master is writable.
Table 2: MS/TP Bus Objects (Part 4 of 4)
Point Name Thermostat Point
(Type/Address)
Range