TEC Series BACnet® MS/TP Network Temperature and Humidity Controllers Technical Bulletin 27
Fan Lock Alarm
4
BI 40 0 = Off
1 = On
Occupied Heat Setpoint
2,
7
AV 42 40.0°F/4.5°C to
90.0°F/32.0°C
Occupied Cool Setpoint
2,
7
AV 43 54.0°F/12.0°C to
100.0°F/37.5°C
Unoccupied Heat Setpoint
2,
7
AV 44 40.0°F/4.5°C to
90.0°F/32.0°C
Unoccupied Cool Setpoint
2,
7
AV 45 54.0°F/12.0°C to
100.0°F/37.5°C
Temperature Scale
2
BV 47 0 = °C
1 = °F
Heating Setpoint Limit
2
AV 48 40.0°F/4.5°C to
90.0°F/32.0°C
Cooling Setpoint Limit
2
AV 49 54.0°F/12.0°C to
100.0°F/37.5°C
Heating Lockout Temperature
2
AV 50 -15.0°F/-26.0°C to
120.0°F/49.0°C
Cooling Lockout Temperature
2
AV 51 -40.0°F/-40.0°C to
95.0°F/35.0°C
Deadband
2
AV 52 2.0F°/1.0C° to 4.0F°/2.0C°
Heating CPH
2
MV 53 1 = 3 CPH
2 = 4 CPH
3 = 5 CPH
4 = 6 CPH
5 = 7 CPH
6 = 8 CPH
Cooling CPH
2
MV 54 1 = 3 CPH
2 = 4 CPH
Frost Protection
2
BV 55 0 = Off
1 = On
Aux Contact
2
BV 56 0 = Normally Open (N.O.)
1 = Normally Closed (N.C.)
Menu Scroll
2
BV 57 0 = No Scroll
1 = Scroll Active
Password Value AV 59 0 to 1,000
Power Up Delay
2
AV 60 10 to 120 Seconds
Temporary Occupancy Time
2
MV 61 1 = 0 Hours
2 = 1 Hour
3 = 2 Hours
4 = 3 Hours
5 = 4 Hours
6 = 5 Hours
7 = 6 Hours
8 = 7 Hours
9 = 8 Hours
10 = 9 Hours
11 = 10 Hours
12 = 11 Hours
13 = 12 Hours
Table 6: TEC2601-4 and TEC2601-4+PIR MS/TP Bus Objects (Part 2 of 3)
Point Name Thermostat Point
(Type/Address)
Range