TEC Series BACnet® MS/TP Network Temperature and Humidity Controllers Technical Bulletin 11
MS/TP Bus Objects Tables
TEC26x6(H)-4 and TEC26x6H-4+PIR Series Thermostat Controllers
Table 3: TEC26x6(H)-4 and TEC26x6H-4+PIR Series MS/TP Bus Objects
(Part 1 of 7)
Point Name Thermostat Point
(Type/Address)
Range
Room Temp
1, 2
AV 7 -40.0°F/-40.0°C to
122.0°F/50.0°C
Room Temp Override
3
BV 8 0 = Normal
1 = Override
Outdoor Temperature
3, 4
AV 9 -40.0°F/-40.0°C to
122.0°F/50.0°C
Room Humidity
(TEC2636-4, TEC2636H-4,
TEC2636H-4+PIR, TEC2656-4,
TEC2656H-4, and
TEC2656H-4+PIR Models)
AV 10 5 to 90% RH
Room Humidity Override
(TEC2636-4, TEC2636H-4,
TEC2636H-4+PIR, TEC2656-4,
TEC2656H-4, and
TEC2656H-4+PIR Models)
BV 11 0 = Normal
1 = Override
Supply Temperature
5
AI 12 -40.0°F/-40.0°C to
122.0°F/50.0°C
Dehumidification Lockout
(TEC2636-4, TEC2636H-4,
TEC2636H-4+PIR, TEC2656-4,
TEC2656H-4, and
TEC2656H-4+PIR Models)
BV 13 0 = Disabled
1 = Enabled
AUX Command
3
BV 14 0 = Off
1=On
Sequence of Operation
3
MSV 15 1 = Cooling Only
2 = Heating Only
3 = Cooling and Reheat
4 = Heating and Reheat
5 = Cool/Heat Four-Pipe
6 = Cool/Heat Four-Pipe and Reheat
System Mode
3
MSV 16 1 = Off
2=Auto
3 = Cool
4 = Heat