TEC Series BACnet® MS/TP Network Temperature and Humidity Controllers Technical Bulletin 39
Temporary Occupancy Time
2
MV 61 1 = 0 Hours
2 = 1 Hour
3 = 2 Hours
4 = 3 Hours
5 = 4 Hours
6 = 5 Hours
7 = 6 Hours
8 = 7 Hours
9 = 8 Hours
10 = 9 Hours
11 = 10 Hours
12 = 11 Hours
13 = 12 Hours
Fan Control
2
BV 62 0 = Off
1 = On
Anticycle
2
MV 63 1 = 0 Minutes
2 = 1 Minute
3 = 2 Minutes
4 = 3 Minutes
5 = 4 Minutes
6 = 5 Minutes
Fan Purge Delay
2
BV 64 0 = Off
1 = On
DI Configuration
2
MV 65 1 = None
2 = Rem NSB
3 = RemOVR
4 = Filter
5 = Service
6 = Fan Lock
Proportional Band MSV 67 1 = 2 (2°F/1.1°C)
2 = 3 (3°F/1.7°C)
3 = 4 (4°F/2.2°C)
4 = 5 (5°F/2.8°C)
5 = 6 (6°F/3.3°C)
6 = 7 (7°F/3.9°C)
7 = 8 (8°F/4.4°C)
Unoccupied Time
4
AV 68 0.5 Hours to
24.0 Hours
Heating Stages
2
MV 73 1 = One Stage
2 = Two Stages
Cooling Stages
2
MV 74 1 = One Stage
2 = Two Stages
RH Display
2
BV 88 0 = Not Activated
1 = Activated
Dehumidification RH Setpoint
2
AV 89 15 to 95%
Dehumidification Hysteresis AV 90 2 to 20%
Dehumidification Low OA
Lockout
AV 91 -40.0°F/-40.0°C to
122.0°F/50.0°C
Dehumidification Lockout
Functions
2
BV 92 0 = Not Activated
1 = Activated
Dehumidification Output
Status
4
BI 93 0 = Off
1 = On
Humidification RH Setpoint
2
AV 95 10 to 90%
Table 9: TEC2613-4 and TEC2613-4+PIR MS/TP Bus Objects (Part 3 of 4)
Point Name Controller Point
(Type/Address)
Range