TEC3000 Series Networked and Wireless Proportional Fan Coil and
Individual Zone Thermostat Controllers with Dehumidification Capability
Quick Start Guide
1
Refer to the QuickLIT website for the most up-to-date version of this document.
North American emissions compliance
United States
Canada
Installation
Parts included
One TEC3000 Series Thermostat Controller with integral mounting base
One installation instructions sheet
Location considerations
For networked models, locate the TEC3000 Series Thermostat Controller:
On a partitioning wall, approximately 5 ft (1.5 m) above the floor in a location of average temperature, allowing
for vertical air circulation to the TEC
Away from direct sunlight, radiant heat, outside walls, outside doors, air discharge grills, stairwells, and
from
b
ehind doors
Away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of
electrical interference
In a clear path between the integrated passive infrared (PIR) occupancy sensor (if equipped) and the spac
e
be
ing monitored
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part
15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in
a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception, which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
This Class (B) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment
Regulations.
Cet appareil numérique de la Classe (B) respecte toutes les exigences du Règlement sur le matériel brouilleur
du Canada.
TEC3000 Series Networked and Wireless Proportional Fan
Coil and Individual Zone Thermostat Controllers with
Dehumidification Capability
Quick Start Guide
TEC3322-1x-xxx, TEC3323-1x-xxx, TEC3622-1x-xxx, TEC3623-1x-xxx, TEC3022-1x-xxx, TEC3023-1x-xxx
Part No. 24-11353-00028, Rev.
C
Issued May 2019
(barcode for factory use only)
24-11353-00028, Rev. C
*241135300028C*

Other manuals for Johnson Controls TEC3000 Series

Questions and Answers

  • W
    whitejosephSep 4, 2025
    How to fix rapid cycling with PID on my Johnson Controls Thermostat?
    • A
      Alex WilliamsSep 5, 2025
      If the staged equipment cycles too rapidly or slowly on your Johnson Controls Thermostat when the PID is running, it may be due to the control band around the setpoint being set incorrectly. Verify that the equipment's minimum on/off times are set correctly. If the default deadband doesn't provide the required temperature control, set 'Temp Control Setup' to 'Deadband Override' and adjust the 'Deadband' parameter to your preferred value.
  • N
    nolsonSep 12, 2025
    What should I do if the changeover temperature on my Johnson Controls Fan is sensing a hot supply, but the controller is requesting cooling?
    • S
      Samantha ClarkSep 12, 2025
      First, verify that the supply is not in heating mode. If it is, nothing can be done from the TEC. Check the wiring of the supply temperature sensor or switch. Check the placement of the supply temperature sensor or switch. Verify that the changeover is set up correctly for the type of sensor attached (sensor or switch).
  • S
    Shannon TateAug 26, 2025
    What causes Fan Lock on Johnson Controls TEC3000 Thermostat and how to resolve it?
    • A
      Amy SmithAug 26, 2025
      If your Johnson Controls Thermostat displays 'Fan Lock', the switch connected to the BI configured for Fan Lock didn't sense airflow within 10 seconds of starting the fan, and control has been shut down. To resolve this: 1. Inspect equipment to ensure fan functions. 2. Check sensor functionality with an ohmmeter, and verify wiring to the TEC. 3. Reset fault by entering the menu, selecting Fault Status, and selecting the Fan Lock. 4. Order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • J
    Jessica HughesSep 13, 2025
    How to fix 'The controller displays Board Mismatch' on Johnson Controls Controller?
    • D
      Dale GutierrezSep 13, 2025
      If your Johnson Controls Controller displays 'The controller displays Board Mismatch', attach the display board to the correct I/O board. If a hardware failure causes the two boards to incorrectly identify themselves, order replacement units and return the affected devices to Johnson Controls under the RMA program. This error occurs because the I/O board that the display board is currently attached to does not match the one that initially shipped with the display board.
  • D
    Dennis DavisSep 23, 2025
    Why does my Johnson Controls Controller display Idle with Cooling/Heating Unavailable due to Control Mode?
    • B
      Bradley RobertsSep 23, 2025
      If your Johnson Controls Controller displays 'Idle' with a Unit Status of 'Cooling Unavailable due to Control Mode' (despite being above the cooling setpoint) or 'Heating Unavailable due to Control Mode' (despite being below the setpoint), it indicates that the Control Mode is set incorrectly. If the Control Mode is set to Cooling Mode, but the controller is requesting heating, change the Control Mode to Auto or Heating. If the Control Mode is set to Heating Mode, but the controller is requesting cooling, change the Control Mode to Auto or Cooling.
  • S
    Sean HarrellSep 23, 2025
    Why does my Johnson Controls Controller display Idle with Cooling/Heating Unavailable due to Changeover?
    • R
      Robert HallSep 23, 2025
      If your Johnson Controls Controller displays 'Idle' with a Unit Status of 'Cooling Unavailable due to Changeover' (despite being above the cooling setpoint) or 'Heating Unavailable due to Changeover' (despite being below the setpoint), it indicates that the two-pipe fan coil/VAV system does not have a changeover sensor and switch connected, or the sensor/switch has failed. To resolve this: 1. Check the wiring of the supply temperature sensor/switch. 2. Verify that the changeover is set up correctly for the type of sensor attached (sensor or switch).
  • J
    johnramirezSep 7, 2025
    What to do if the Johnson Controls Fan is in Fan Lock?
    • H
      Heather RomeroSep 7, 2025
      If your Johnson Controls Fan is in Fan Lock, it means the switch connected to the BI configured for Fan Lock didn't detect airflow within 10 seconds of the fan starting, which shut down control. Here's what to do: 1. Check the equipment to make sure the fan is working. 2. Use an ohmmeter to check the sensor and verify the wiring to the TEC. 3. Reset the fault by going to the menu, selecting Fault Status, and then Fan Lock. 4. If the problem persists, order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • C
    craigandreaSep 23, 2025
    What does Internal Sensor Fail mean on my Johnson Controls Controller?
    • D
      Dr. Sean GarciaSep 23, 2025
      If your Johnson Controls Controller displays 'Internal Sensor Fail', it means an internal sensor has failed on the TEC. Order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • C
    Christopher WiseSep 18, 2025
    Why does my staged equipment cycle too fast or slow with PID on my Johnson Controls Controller?
    • M
      Ms. Angela DeleonSep 18, 2025
      If the staged equipment on your Johnson Controls Controller cycles too rapidly or slowly when the PID is running, the control band around the setpoint is likely set incorrectly for your equipment, zone, or preference. Verify that the equipment's minimum on/off times are set correctly. If the default deadband doesn't provide the desired temperature control, set Temp Control Setup to Deadband Override and adjust the Deadband parameter to your preferred value.
  • L
    lsloanSep 12, 2025
    What should I do if my Johnson Controls Fan controller displays 'Controller Fault'?
    • D
      Desiree HollowaySep 12, 2025
      If your Johnson Controls Fan controller displays 'Controller Fault', it means an internal fault was detected and the controller was unable to recover. Order replacement units and return the affected devices to Johnson Controls under the RMA program.

Summary

Installation Procedures

Optimal Location Considerations

Guidelines for selecting the best placement for controller performance.

Mounting and Securing the Controller

Step-by-step guide for physically installing the thermostat controller.

Wiring Procedures and Safety

Electrical Safety and Precautions

Warnings about shock hazards, property damage, and ESD during wiring.

Terminal Connections and EOL Setup

Instructions for wiring terminals and setting the bus end-of-line switch.

Setup and Display Customization

User Interface and Operational Features

USB Port for Firmware and Backups

Guide for using the USB port for upgrades, backups, and restoring settings.

Controller Configuration and Modes

Scheduling and Occupancy Control

Troubleshooting Common Issues

Diagnosing and Resolving Faults

Lists common faults, their causes, and recommended solutions.

Symptom-Based Troubleshooting Guide

Detailed steps to diagnose and fix specific operational problems.