EasyManuals Logo

Johnson Controls York YCAL0014E Series User Manual

Johnson Controls York YCAL0014E Series
216 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #104 background imageLoading...
Page #104 background image
JOHNSON CONTROLS
104
FORM 150.62-NM6 (103)
SYSTEM LEAD/LAG
Lead/lag between systems may be selected to help
equalize average run hours between systems on chill-
ers with 2 refrigerant systems. This may be programmed
under the OPTIONS key. Auto lead/lag allows automatic
lead/lag of the two systems based on average run hours
of the compressors in each system. Manual lead/lag
selects specically the sequence in which the micro
starts systems.
COMPRESSOR LEAD/LAG
The compressors within a system rotate starts in se-
quence 1, 2 or 1, 2, 3 with wraparound. The longest-off
compressor in a system will start rst, and the longest-
running compressor in a system will turn off rst. When
unloading, the system with the most compressors on,
unloads rst. The lag system will shut down a com-
pressor rst when equal numbers of compressors are
operating in each system. The micro will not attempt to
equalize run time of compressors in a system.
Once the second system has started a compressor, the
micro will attempt to equally load each system. Once this
occurs, loading will alternate between systems.
If Soft Start is enabled on European models with this
option, compressor lead/lag will function as outlined in
Option 12 under the Options key.
ANTI-RECYCLE TIMER
The programmable anti-recycle timer assures that sys-
tems do not cycle. This timer is programmable under the
PROGRAM key between 300 - 600 seconds. Whenever
possible, to reduce cycling and motor heating, the anti-
recycle timer should be adjusted to 600 seconds. The
programmable anti-recycle timer starts the timer when
the rst compressor in a system starts. The timer begins
to count down. If all of the compressors in a circuit cycle
off, a compressor within the circuit will not be permitted to
start until the anti-recycle timer has timed out. If the lead
system has run for less than 5 minutes, 3 times in a row,
the anti-recycle timer will be extended to 10 minutes.
ANTI-COINCIDENCE TIMER
This timer is not present on single-system units. Two
timing controls are present in software to assure com-
pressors within a circuit or between systems, do not start
simultaneously. The anti-coincidence timer assures there
is at least a one minute delay between system starts on
2-circuit systems. This timer is NOT programmable. The
load timers further assure that there is a minimum time
between compressor starts within a system.
EVAPORATOR PUMP CONTROL
The evaporator pump dry contacts (CTB2 – terminals
23 - 24) are energized when any of the following con-
ditions are true:
Unit Controls
Notes:
1. Step 1 is Hot Gas Bypass and is skipped when loading occurs. Hot Gas Bypass operation is inhibited during Pumpdown.
2. Step 3 is skipped when loading occurs.
3. Step 4 is skipped when unloading occurs.
TABLE 26 – RETURN CHILLED LIQUID CONTROL FOR 4 COMPRESSORS (6 STEPS)
*STEP COMPRESSOR COMPRESSOR ON POINT COMPRESSOR OFF POINT
0 0 SETPOINT SETPOINT
1 1 W/HGB SP + CR/8 (Note 1) SETPOINT
2 1 NO HGB SP + CR/4 SP + CR/8
3 2 SP + 2*CR/4 (Note 2) SP + CR/4
4 2 SP + 2*CR/4 SP + CR/4 (Note 3)
5 3 SP + 3*CR/4 SP + 2*CR/4
6 4 SP + CR SP + 3*CR/4
* STEP can be viewed using the OPER DATA key and scrolling to COOLING DEMAND.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls York YCAL0014E Series and is the answer not in the manual?

Johnson Controls York YCAL0014E Series Specifications

General IconGeneral
BrandJohnson Controls
ModelYork YCAL0014E Series
CategoryChiller
LanguageEnglish

Related product manuals