EasyManua.ls Logo

Johnson Controls York YKN2Open board - Page 34

Johnson Controls York YKN2Open board
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
J2 (Supply), J3 (Suction), J4 (Liquid), J6 (Outdoor), J13 (Water and return)
Temperature Heater Voltage
Temperature Heater Voltage
(°C) (Ohms) (V) (°C) (Ohms) (V)
59 2582 0,95052
105 586 0,25289
60 2490 0,92291
106 569 0,24592
61 2402 0,89613
107 553 0,23933
62 2318 0,87025
108 538 0,23314
63 2237 0,84498
109 523 0,22694
64 2159 0,82035
110 509 0,22113
65 2085 0,79671
111 495 0,21531
66 2013 0,77346
112 481 0,20948
67 1944 0,75093
11 3 468 0,20405
68 1878 0,72915
114 455 0,19860
69 1814 0,70782
115 443 0,19357
70 1753 0,68729
116 431 0,18852
71 1694 0,66724
117 419 0,18347
72 1638 0,64805
118 408 0,17882
73 1583 0,62902
119 397 0,17417
74 1531 0,61089
120 387 0,16993
75 1481 0,59330
121 377 0,16569
76 1433 0,57629
122 367 0,16143
77 1386 0,55950
12 3 357 0,15717
78 1341 0,54331
124 348 0,15333
79 1298 0,52773
125 339 0,14948
80 1256 0,51240
126 330 0,14563
81 1216 0,49771
127 322 0,14220
82 1178 0,48366
128 314 0,13877
83 1141 0,46990
129 306 0,13533
84 1105 0,45642
130 298 0,13188
85 1070 0,44325
131 291 0,12886
86 1037 0,43076
132 283 0,12541
87 1005 0,41858
133 276 0,12238
88 974 0,40671
134 270 0,11979
89 944 0,39518
135 263 0,11675
90 915 0,38397
136 256 0,11372
91 888 0,37349
137 250 0,11111
92 861 0,36295
138 244 0,10850
93 853 0,35982
139 238 0,10589
94 810 0,34293
140 232 0,10328
95 786 0,33345
141 226,8 0,10101
96 763 0,32432
142 221,6 0,09874
97 740 0,31516
14 3 216,4 0,09647
98 719 0,30677
144 211,2 0,09419
99 698 0,29834
145 206 0,09192
100 677 0,28989
146 201,4 0,08990
101 658 0,28221
147 196,8 0,08788
102 639 0,27451
148 192,2 0,08586
103 621 0,26719
149 187,6 0,08384
104 603 0,25985 150 183 0,08182
N O T E
Reading of the value:
Resistance value in Ω, with the probe disconnected from the YKN2Open board.
Voltage value in Ω, with the probe connected to the YKN2Open board between two terminals of the
probe.
Temperature tables
7
Tables 7.1
31

Related product manuals