Units without pack
YLHA
Characteristics 40 50 60 80 100 120 150
Start-up current (compressor) A 174 118 118 174 118 118 174
Pressure drop, cooling mode kPa 70 37 51 56 53 29,5 25,5
Unit water content 4 6 6 7 12 12 14
Max. unit power supply consumption kW 16,3 23 24,8 32,6 50 53 71,1
Max. current amperage A 34,3 43,3 46,3 66,6 91 103 114
Weight (1) kg 337 537 568 735 1154 1220 1445
(1) Weights for the empty unit
1.5.4 Electrical specifications
The use of
Softstart
reduces the start-up current by 40%.
Model
Power supply [V /
ph (Hz)]
Compressor Fans Pump
Rated current [A]
Start-up
current [A]
Standard Rating [kW]
Rated current
[A]
Standard Rat‐
ing [kW]
Rated cur‐
rent [A]
Standard
Rating [kW]
Cold Heat Cold Heat
YLCA 40
400/3 (50)
21,7
-
174
12,46 -
2 x 1.9 2 x 400 1,9 1035
YLHA 40 25,8 24,5 12,49 11,7
YLCA 50 2 x 15.5 -
118
2 x 8.5 -
2 x 2.8 2 x 600 1,8 990
YLHA 50 2 x 15 2 x 15.3 2 x 8 2 x 8.3
YLCA 60 2 x 16.7 - 2 x 9.20 -
2 x 2.8 2 x 600 2,9 1515
YLHA 60 2 x 16.7 2 x 16.7 2 x 9.20 2 x 9.20
YLCA 80 2 x 24.6 -
174
2 x 12.4 -
3 x 2.8 3 x 600
3,3 1620
YLHA 80 2 x 24.9 2 x 24.6 2 x 12.1 2 x 12.2 3,2 1580
YLCA 100 4 x 16 -
118
4 x 7.8 -
4 x 2.8 4 x 600
4,4 2395
YLHA 100 4 x 16 4 x 15.5 4 x 8.3 4 x 8.4
YLCA 120 4 x 17.7 - 4 x 9.4 -
5,5 3180
YLHA 120 4 x 18.2 4 x 16.9 4 x 10.2 4 x 9.2
YLCA 150 4 x 23.5 -
174
4 x 12.53 -
4 x 3.9 4 x 860 6,1 3400
YLHA 150 4 x 23.5 4 x 24.5 4 x 11.8 4 x 12.5
Quick installation guide 1
Technical data 1.5
21