N O T E
The capacity table shows net values according to the EUROVENT EN14511:2011 certification.
Contact your sales representative / distributor to obtain net values according to the EUROVENT
EN14511:2011 certification.
Abs. power = Includes compressor and fan consumption.
1.9 Instructions for installation and connection of the unit
1.9.1 Characteristics of the location
Before locating the unit, make sure you have received the appropriate product by checking the
specifications described on the outside of same.
The unit should be placed on a perfectly horizontal plane, making sure the base can support the weight
of the unit.
If vibration-free operation is required, the unit can be placed on a cork or similar anti-vibratory base, or
fastened to the base with anti-vibratory plates or supports.
1.9.2 Specifications for the foundation or anchoring of the unit
Where the unit is to be installed at ground level, the
characteristics of the ground it will sit on must be taken
into account.
Characteristics, such as acceptable surface firmness,
must be suitable for the foundation the unit requires.
1.9.3 Hydraulic connections
A T T E N T I O N
The water filter must be used whilst the unit is in operation.
A T T E N T I O N
The water circuit connected to the unit must be thoroughly cleaned, in order to prevent dirt from reaching
the plate heat exchanger.
The hydraulic connections of the water inlet and outlet of the unit should be carried out respecting the
inlet and outlet directions indicated.
Galvanised iron or copper piping can be used, with dimensions no lower than those indicated, and
keeping in mind the pressure drops at said connections and in the internal exchanger of the installation.
The pipes and connections should be supplied separately to prevent charges in the heat exchangers.
Flexible connections are recommended to minimise the transmission of vibrations to the structure. They
should be used if the unit is mounted on antivibration supports and if movements of the unit are planned
in normal operation.
Pump dimensioning should be carried out in accordance with a nominal flow rate that allows a Δt within
the operating limits.