5167515-YIM-H-0518
22 Johnson Controls Ducted Systems
120
(10)
208 16.0 110.0 24.9 3.0 6.8 5.5 0.0
None-- -48.954.460 70
E18 13.5 2 37.5 55.3 62.2 60 70
E24 18.0 2 50.0 71.0 77.8 80 80
E36 25.5 2 70.8 97.0 103.9 100 110
E54 40.6 2 112.7 149.4 156.2 150 175
230 16.0 110.0 24.9 3.0 6.8 5.5 0.0
None-- -48.954.460 70
E18 18.0 2 43.3 62.6 69.5 70 70
E24 24.0 2 57.7 80.7 87.5 90 90
E36 34.0 2 81.8 110.7 117.6 125 125
E54 54.0 2 129.9 138.4 145.3 150 175
460 7.8 52.0 12.1 1.6 3.4 2.2 0.0
None-- -24.226.430 30
E18 18.0 2 21.7 31.3 34.1 35 35
E24 24.0 2 28.9 40.3 43.1 45 45
E36 34.0 2 40.9 55.4 58.1 60 60
E54 54.0 2 65.0 69.2 72.0 80 80
575 5.7 38.9 8.9 1.4 2.4 1.8 0.0
None-- -17.919.720 25
E18 18.0 2 17.3 24.7 26.9 25 30
E24 24.0 2 23.1 31.9 34.1 35 35
E36 34.0 2 32.7 43.9 46.1 45 50
E54 54.0 2 52.0 55.0 57.2 60 60
150
(12.5)
208 23.1 160.0 36.0 2.1 9.6 5.5 0.0
None-- -70.075.590 90
E18 13.5 2 37.5 70.0 75.5 90 90
E24 18.0 2 50.0 74.5 81.3 90 90
E36 25.5 2 70.8 100.5 107.4 110 110
E54 40.6 2 112.7 152.9 159.7 175 175
230 23.1 160.0 36.0 2.1 9.6 5.5 0.0
None-- -70.075.590 90
E18 18.0 2 43.3 70.0 75.5 90 90
E24 24.0 2 57.7 84.2 91.0 90 100
E36 34.0 2 81.8 114.2 121.1 125 125
E54 54.0 2 129.9 141.9 148.8 175 175
460 12.2 87.0 19.0 1.3 4.7 2.2 0.0
None-- -37.239.445 50
E18 18.0 2 21.7 37.2 39.4 45 50
E24 24.0 2 28.9 42.0 44.7 45 50
E36 34.0 2 40.9 57.0 59.7 60 60
E54 54.0 2 65.0 70.8 73.6 80 80
575 8.7 62.0 13.5 0.7 3.6 1.8 0.0
None-- -25.827.630 35
E18 18.0 2 17.3 26.2 28.4 30 35
E24 24.0 2 23.1 33.4 35.6 35 40
E36 34.0 2 32.7 45.4 47.6 50 50
E54 54.0 2 52.0 56.5 58.7 70 70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZH078-150 Standard Motor - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
MCA
1
w/Pwr
Exh
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
Max Fuse
2
/
Breaker
3
Size w/
Pwr Exh
(Amps)
RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps