Table 9: ZY04 to 12 Standard Static Indoor Blower - Without Powered Convenience Outlet
Compressor 1 Compressor 2
Electric Heat Field
Installed Kit 2EK045*
4
Min Disconnect Rating
Min Disconnect Rating/ Pwr Exh
Size (Tons)
Nominal Unit Voltage
RLA LRA MCC RLA LRA MCC
OD Fan Motors (each)
Supply Blower Motor
Pwr Exh Motor
Pwr Conv Outlet
Model kW Stages Amps
1
MCA (Amps)
2,3
Min Fuse/ Breaker Size (Amps)
Max Fuse/ Breaker Size (Amps)
FLA LRA
MCA w/Pwr Exh (Amps)
Min Fuse/ Breaker Size w/ Pwr Exh (Amps)
Max Fuse/ Breaker Size w/ Pwr Exh (Amps)
FLA LRA
None - - - 42 45 60 41 141 43.5 45 60 43 144
10625 4.9 1 23.6 42 45 60 41 141 43.5 45 60 43 144208-1-60 25 134 39 2.3 8.4 1.5
11125 7.9 1 38 58 60 60 53 141 59.9 60 60 55 144
None - - - 41.2 45 60 40 141 42.5 45 60 42 144
10625 6.5 1 27.1 43.4 45 60 40 141 45 45 60 42 144230-1-60 25 134 39 2.3 7.6 1.3
11125 10.5 1 43.8 64.3 70 70 59 141 65.9 70 70 61 144
None - - - 30.6 35 45 31 117 31.7 35 45 32 119
10625 4.9 1 13.6 30.6 35 45 31 117 31.7 35 45 32 119
11125 7.9 1 21.9 37.9 40 45 35 117 39.3 40 45 36 119
208-3-60 15.9 110 25 2.3 8.4 1.1
11625 12 1 33.3 52.1 60 60 48 117 53.5 60 60 49 119
None - - - 29.8 30 45 30 117 30.8 35 45 31 119
10625 6.5 1 15.6 29.8 30 45 30 117 30.8 35 45 31 119
11125 10.5 1 25.3 41.1 45 45 38 117 42.4 45 45 39 119
230-3-60 15.9 110 25 2.3 7.6 1
11625 16 1 38.5 57.6 60 60 53 117 58.9 60 60 54 119
None - - - 14.2 15 20 14 57 14.7 15 20 15 58
11146 6 1 7.2 14.2 15 20 13 57 14.7 15 20 13 58
11146 11.5 1 13.8 22.3 25 25 20 57 22.9 25 25 21 58
460-3-60 7.1 52 11 1.3 4 0.5
11446 14 1 16.8 26 30 30 24 57 26.6 30 30 24 58
None - - - 10.5 15 15 11 43 10.9 15 15 11 44
11458 13.8 1 13.3 20.4 25 25 19 43 20.9 25 25 19 44
06 (5)
575-3-60 5.1 39.5 8 1.1 7.6 0.4
12358 23 1 22.1 31.4 35 35 29 43 31.9 35 35 29 44
None - - - 33.6 35 50 33 165 35.8 40 50 36 175
10725 4.9 1 13.6 33.6 35 50 33 165 35.8 40 50 36 175
11725 12 1 33.3 48.1 50 50 44 165 50.9 60 60 47 175
208-3-60 19 123 30 2.3 5.2 1.1
12525 18.6 1 51.6 71 80 80 65 165 73.8 80 80 68 175
None - - - 33.6 35 50 33 168 35.6 40 50 35 163
10725 6.5 1 15.6 33.6 35 50 33 168 35.6 40 50 35 163
11725 16 1 38.5 54.6 60 60 50 168 57.1 60 60 53 163
230-3-60 19 123 30 2.3 5.2 1
12525 24.8 1 59.7 81.1 90 90 75 168 83.6 90 90 77 163
None - - - 17.3 20 25 17 86 18.3 20 25 18 83
10746 6 1 7.2 17.3 20 25 11 86 18.3 20 25 12 83
11746 16.5 1 19.8 28 30 30 26 86 29.3 30 30 27 83
460-3-60 9.7 62 15 1.3 2.6 0.5
12646 25.5 1 30.7 41.6 45 45 38 86 42.9 45 45 39 83
None - - - 13.5 15 20 13 69 14.3 15 20 14 67
11758 17 1 16.4 23 25 25 21 69 24 25 25 22 67
07 (6)
575-3-60 7.4 50 12 1.1 2 0.4
12658 25.7 1 24.7 33.4 35 35 31 69 34.4 35 35 32 67
None - - - 31.8 35 45 32 168 34 35 50 34 173
10725 4.9 1 13.6 31.8 35 45 32 168 34 35 50 34 173
11725 12 1 33.3 48.1 50 50 44 168 50.9 60 60 47 173
208-3-60 17.6 136 27 2.3 5.2 1.1
12525 18.6 1 51.6 71 80 80 65 168 73.8 80 80 68 173
None - - - 31.8 35 45 32 171 33.8 35 50 34 176
10725 6.5 1 15.6 31.8 35 45 32 171 33.8 35 50 34 176
11725 16 1 38.5 54.6 60 60 50 171 57.1 60 60 53 176
230-3-60 17.6 136 27 2.3 5.2 1
12525 24.8 1 59.7 81.1 90 90 75 171 83.6 90 90 77 176
None - - - 15.8 20 20 16 84 16.8 20 20 17 87
10746 6 1 7.2 15.8 20 20 11 84 16.8 20 20 12 87
11746 16.5 1 19.8 28 30 30 26 84 29.3 30 30 27 87
460-3-60 8.5 66.1 13 1.3 2.6 0.5
12646 25.5 1 30.7 41.6 45 45 38 84 42.9 45 45 39 87
None - - - 12.1 15 15 12 70 12.9 15 15 13 72
11758 17 1 16.4 23 25 25 21 70 24 25 25 22 72
A7 (6)
575-3-60 6.3 55.3 10 1.1 2 0.4
12658 25.7 1 24.7 33.4 35 35 31 70 34.4 35 35 32 72
INSTALLATION MANUAL ZY SERIES 3-10ton 60 Hertz R-410A30