ZY04 to 12 Medium Static Indoor Blower - Without Powered Convenience Outlet
Table 11: ZY04 to 12 Medium Static Indoor Blower - Without Powered Convenience Outlet
Compressor 1 Compressor 2
Electric Heat Field
Installed Kit 2EK045*
4
Min Disconnect Rating
Min Disconnect Rating/ Pwr Exh
Size (Tons)
Nominal Unit Voltage
RLA LRA MCC RLA LRA MCC
OD Fan Motors (each)
Supply Blower Motor
Pwr Exh Motor
Pwr Conv Outlet
Model kW Stages Amps
1
MCA (Amps)
2,3
Min Fuse/ Breaker Size (Amps)
Max Fuse/ Breaker Size (Amps)
FLA LRA
MCA w/Pwr Exh (Amps)
Min Fuse/ Breaker Size w/ Pwr Exh (Amps)
Max Fuse/ Breaker Size w/ Pwr Exh (Amps)
FLA LRA
None - - - 29.9 30 45 30 115 31.4 35 45 31 119
10625 4.9 1 23.6 39 40 45 36 115 40.9 45 45 38 119208-1-60 16.7 79 26 1.4 7.6 1.5
11125 7.9 1 38 57 60 60 52 115 58.9 60 60 54 119
None - - - 29.3 30 45 29 118 30.6 35 45 30 121
10625 6.5 1 27.1 42.6 45 45 39 118 44.3 45 45 41 121230-1-60 16.7 79 26 1.4 7 1.3
11125 10.5 1 43.8 63.5 70 70 58 118 65.1 70 70 60 121
None - - - 19.6 20 30 20 99 20.7 25 30 21 101
10625 4.9 1 13.6 23.5 25 30 22 99 24.9 25 30 23 101
11125 7.9 1 21.9 33.9 35 35 31 99 35.3 40 40 32 101
208-3-60 10.4 73 16 1.4 5.2 1.1
11625 12 1 33.3 48.1 50 50 44 99 49.5 50 50 46 101
None - - - 19.6 20 30 20 101 20.6 25 30 21 104
10625 6.5 1 15.6 26 30 30 24 101 27.3 30 30 25 104
11125 10.5 1 25.3 38.1 40 40 35 101 39.4 40 40 36 104
230-3-60 10.4 73 16 1.4 5.2 1
11625 16 1 38.5 54.6 60 60 50 101 55.9 60 60 51 104
None - - - 10.7 15 15 11 52 11.2 15 15 11 54
10646 6 1 7.2 12.3 15 15 11 52 12.9 15 15 12 54
11146 11.5 1 13.8 20.5 25 25 19 52 21.1 25 25 19 54
460-3-60 5.8 38 9 0.8 2.6 0.5
11446 14 1 16.8 24.3 25 25 22 52 24.9 25 25 23 54
None - - - 7.4 15 15 7 48 7.8 15 15 8 49
11058 9.2 1 8.9 13.6 15 15 13 48 14.1 15 15 13 49
04 (3)
575-3-60 3.8 36.5 6 0.6 2 0.4
11458 13.8 1 13.3 19.1 20 20 18 48 19.6 20 20 18 49
None - - - 36.3 40 50 35 153 37.8 40 50 37 157
10625 4.9 1 23.6 39 40 50 36 153 40.9 45 50 38 157208-1-60 21.8 117 34 1.4 7.6 1.5
11125 7.9 1 38 57 60 60 52 153 58.9 60 60 54 157
None - - - 35.7 40 50 35 156 37 40 50 36 159
10625 6.5 1 27.1 42.6 45 50 39 156 44.3 45 50 41 159230-1-60 21.8 117 34 1.4 7 1.3
11125 10.5 1 43.8 63.5 70 70 58 156 65.1 70 70 60 159
None - - - 23.7 25 35 23 109 24.8 25 35 25 111
10625 4.9 1 13.6 23.7 25 35 23 109 24.9 25 35 25 111
11125 7.9 1 21.9 33.9 35 35 31 109 35.3 40 40 32 111
208-3-60 13.7 83.1 21 1.4 5.2 1.1
11625 12 1 33.3 48.1 50 50 44 109 49.5 50 50 46 111
None - - - 23.7 25 35 23 111 24.7 25 35 24 114
10625 6.5 1 15.6 26 30 35 24 111 27.3 30 35 25 114
11125 10.5 1 25.3 38.1 40 40 35 111 39.4 40 40 36 114
230-3-60 13.7 83.1 21 1.4 5.2 1
11625 16 1 38.5 54.6 60 60 50 111 55.9 60 60 51 114
None - - - 11.2 15 15 11 55 11.7 15 15 12 57
10646 6 1 7.2 12.3 15 15 11 55 12.9 15 15 12 57
11146 11.5 1 13.8 20.5 25 25 19 55 21.1 25 25 19 57
460-3-60 6.2 41 10 0.8 2.6 0.5
11446 14 1 16.8 24.3 25 25 22 55 24.9 25 25 23 57
None - - - 8.6 15 15 9 45 9 15 15 9 45
11058 9.2 1 8.9 13.6 15 15 13 45 14.1 15 15 13 45
05 (4)
575-3-60 4.8 33 8 0.6 2 0.4
11458 13.8 1 13.3 19.1 20 20 18 45 19.6 20 20 18 45
INSTALLATION MANUAL ZY SERIES 3-10ton 60 Hertz R-410A 41
Johnson Controls Ducted Systems

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls ZY Series and is the answer not in the manual?

Johnson Controls ZY Series Specifications

General IconGeneral
BrandJohnson Controls
ModelZY Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals