Table 10: ZY04 to 12 Standard Static Indoor Blower - With Powered Convenience Outlet
Compressor 1 Compressor 2
Electric Heat Field
Installed Kit 2EK045*
4
Min Disconnect Rating
Min Disconnect Rating/ Pwr Exh
Size (Tons)
Nominal Unit Voltage
RLA LRA MCC RLA LRA MCC
OD Fan Motors (each)
Supply Blower Motor
Pwr Exh Motor
Pwr Conv Outlet
Model kW Stages Amps
1
MCA (Amps)
2,3
Min Fuse/ Breaker Size (Amps)
Max Fuse/ Breaker Size (Amps)
FLA LRA
MCA w/Pwr Exh (Amps)
Min Fuse/ Breaker Size w/ Pwr Exh (Amps)
Max Fuse/ Breaker Size w/ Pwr Exh (Amps)
FLA LRA
None - - - 53.1 60 60 56 306 55.3 60 70 59 316
11725 12 1 33.3 55.8 60 60 56 306 58.5 60 70 59 316
12525 18.6 1 51.6 78.6 80 80 72 306 81.4 90 90 75 316
13225 24 1 66.6 97.4 100 100 90 306 100.1 110 110 92 316
208-3-60 16 110 25 16 110 25 5.8 7 1.1 8.6
14225 31.8 2 88.3 124.5 125 125 115 306 127.3 150 150 117 316
None - - - 52.7 60 60 56 305 54.7 60 70 58 310
11725 16 1 38.5 62.5 70 70 58 305 65 70 70 60 310
12525 24.8 1 59.7 89 90 90 82 305 91.5 100 100 84 310
13225 32 1 77 110.6 125 125 102 305 113.1 125 125 104 310
230-3-60 16 110 25 16 110 25 5.2 7.2 1 8.6
14225 42.4 2 102 141.9 150 150 131 305 144.4 150 150 133 310
None - - - 26.3 30 30 28 148 27.3 30 30 29 150
11746 16.5 1 19.8 31.9 35 35 29 148 33.2 35 35 31 150
12846 27.8 1 33.4 48.9 50 50 45 148 50.2 60 60 46 150
13346 33 1 39.7 56.8 60 60 52 148 58.1 60 60 53 150
460-3-60 7.8 52 12 7.8 52 12 2.9 3.6 0.5 8.6
14246 41.7 2 50.2 69.9 70 70 64 148 71.2 80 80 65 150
None - - - 19.2 20 20 20 109 20 20 20 21 110
11758 17 1 16.4 25.8 30 30 24 109 26.8 30 30 25 110
12 (10)
575-3-60 5.7 38.9 9 5.7 38.9 9 2.2 2.5 0.4 8.6
13458 34 1 32.7 46.2 50 50 42 109 47.2 50 50 43 110
1 Minimum Circuit Ampacity.
2 Dual Element, Time Delay Type.
3 HACR type per NEC.
4 Non-fused Disconnect. Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field
installed electric heat kits may exceed the factory installed disconnect amperage rating.