ZY04 to 12 Standard Static Indoor Blower - With Powered Convenience Outlet
Table 10: ZY04 to 12 Standard Static Indoor Blower - With Powered Convenience Outlet
Compressor 1 Compressor 2
Electric Heat Field
Installed Kit 2EK045*
4
Min Disconnect Rating
Min Disconnect Rating/ Pwr Exh
Size (Tons)
Nominal Unit Voltage
RLA LRA MCC RLA LRA MCC
OD Fan Motors (each)
Supply Blower Motor
Pwr Exh Motor
Pwr Conv Outlet
Model kW Stages Amps
1
MCA (Amps)
2,3
Min Fuse/ Breaker Size (Amps)
Max Fuse/ Breaker Size (Amps)
FLA LRA
MCA w/Pwr Exh (Amps)
Min Fuse/ Breaker Size w/ Pwr Exh (Amps)
Max Fuse/ Breaker Size w/ Pwr Exh (Amps)
FLA LRA
None - - - 33.2 35 45 33 89 34.7 35 50 35 92
10625 4.9 1 23.6 43.1 45 45 40 89 45 45 50 41 92208-1-60 16.7 79 26 1.4 6.6 1.5 8.6
11125 7.9 1 38 61.1 70 70 56 89 63 70 70 58 92
None - - - 32.6 35 45 33 89 33.9 35 50 34 92
10625 6.5 1 27.1 46.8 50 50 43 89 48.4 50 50 45 92230-1-60 16.7 79 26 1.4 6 1.3 8.6
11125 10.5 1 43.8 67.6 70 70 62 89 69.3 70 70 64 92
None - - - 25.3 30 35 26 83 26.4 30 35 27 85
10625 4.9 1 13.6 30.6 35 35 28 83 32 35 35 29 85
11125 7.9 1 21.9 41 45 45 38 83 42.4 45 45 39 85
208-3-60 10.4 73 16 1.4 6.6 1.1 8.6
11625 12 1 33.3 55.3 60 60 51 83 56.6 60 60 52 85
None - - - 24.7 25 35 25 83 25.7 30 35 27 85
10625 6.5 1 15.6 32.4 35 35 30 83 33.6 35 35 31 85
11125 10.5 1 25.3 44.5 45 45 41 83 45.8 50 50 42 85
230-3-60 10.4 73 16 1.4 6 1 8.6
11625 16 1 38.5 61 70 70 56 83 62.3 70 70 57 85
None - - - 13.5 15 15 14 44 14 15 15 14 45
10646 6 1 7.2 15.7 20 20 14 44 16.3 20 20 15 45
11146 11.5 1 13.8 23.9 25 25 22 44 24.6 25 25 23 45
460-3-60 5.8 38 9 0.8 3.2 0.5 8.6
11446 14 1 16.8 27.7 30 30 25 44 28.3 30 30 26 45
None - - - 9.5 15 15 10 41 9.9 15 15 10 41
11058 9.2 1 8.9 16.3 20 20 15 41 16.8 20 20 15 41
04 (3)
575-3-60 3.8 36.5 6 0.6 6 0.4 8.6
11458 13.8 1 13.3 21.8 25 25 20 41 22.3 25 25 20 41
None - - - 41.4 45 60 41 127 42.9 45 60 43 130
10625 4.9 1 23.6 45.4 50 60 42 127 47.3 50 60 43 130208-1-60 21.8 117 34 1.4 8.4 1.5 8.6
11125 7.9 1 38 63.4 70 70 58 127 65.3 70 70 60 130
None - - - 40.6 45 60 40 127 41.9 45 60 42 130
10625 6.5 1 27.1 48.8 50 60 45 127 50.4 60 60 46 130230-1-60 21.8 117 34 1.4 7.6 1.3 8.6
11125 10.5 1 43.8 69.6 70 70 64 127 71.3 80 80 66 130
None - - - 31.2 35 40 32 93 32.3 35 45 33 95
10625 4.9 1 13.6 32.9 35 40 32 93 34.3 35 45 33 95
11125 7.9 1 21.9 43.3 45 45 40 93 44.6 45 45 41 95
208-3-60 13.7 83.1 21 1.4 8.4 1.1 8.6
11625 12 1 33.3 57.5 60 60 53 93 58.9 60 60 54 95
None - - - 30.4 35 40 31 93 31.4 35 45 32 95
10625 6.5 1 15.6 34.4 35 40 32 93 35.6 40 45 33 95
11125 10.5 1 25.3 46.5 50 50 43 93 47.8 50 50 44 95
230-3-60 13.7 83.1 21 1.4 7.6 1 8.6
11625 16 1 38.5 63 70 70 58 93 64.3 70 70 59 95
None - - - 14.8 15 20 15 47 15.3 20 20 16 48
10646 6 1 7.2 16.7 20 20 15 47 17.3 20 20 16 48
11146 11.5 1 13.8 24.9 25 25 23 47 25.6 30 30 24 48
460-3-60 6.2 41 10 0.8 4 0.5 8.6
11446 14 1 16.8 28.7 30 30 26 47 29.3 30 30 27 48
None - - - 11.4 15 15 12 37 11.8 15 15 12 38
11058 9.2 1 8.9 17.1 20 20 16 37 17.6 20 20 16 38
05 (4)
575-3-60 4.8 33 8 0.6 7.6 0.4 8.6
11458 13.8 1 13.3 22.6 25 25 21 37 23.1 25 25 21 38
INSTALLATION MANUAL ZY SERIES 3-10ton 60 Hertz R-410A 35
Johnson Controls Ducted Systems

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls ZY Series and is the answer not in the manual?

Johnson Controls ZY Series Specifications

General IconGeneral
BrandJohnson Controls
ModelZY Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals