Table 11: ZY04 to 12 Medium Static Indoor Blower - Without Powered Convenience Outlet
Compressor 1 Compressor 2
Electric Heat Field
Installed Kit 2EK045*
4
Min Disconnect Rating
Min Disconnect Rating/ Pwr Exh
Size (Tons)
Nominal Unit Voltage
RLA LRA MCC RLA LRA MCC
OD Fan Motors (each)
Supply Blower Motor
Pwr Exh Motor
Pwr Conv Outlet
Model kW Stages Amps
1
MCA (Amps)
2,3
Min Fuse/ Breaker Size (Amps)
Max Fuse/ Breaker Size (Amps)
FLA LRA
MCA w/Pwr Exh (Amps)
Min Fuse/ Breaker Size w/ Pwr Exh (Amps)
Max Fuse/ Breaker Size w/ Pwr Exh (Amps)
FLA LRA
None - - - 51.7 60 60 55 315 53.9 60 60 57 325
11725 12 1 33.3 54 60 60 55 315 56.8 60 60 57 325
12525 18.6 1 51.6 76.9 80 80 71 315 79.6 80 80 73 325
13225 24 1 66.6 95.6 100 100 88 315 98.4 100 100 91 325
208-3-60 16 110 25 16 110 25 5.8 9.9 1.1
14225 31.8 2 88.3 122.8 125 125 113 315 125.5 150 150 115 325
None - - - 50.6 60 60 54 320 52.6 60 60 56 324
11725 16 1 38.5 59.9 60 60 55 320 62.4 70 70 57 324
12525 24.8 1 59.7 86.4 90 90 79 320 88.9 90 90 82 324
13225 32 1 77 108 110 110 99 320 110.5 125 125 102 324
230-3-60 16 110 25 16 110 25 5.2 9.4 1
14225 42.4 2 102 139.3 150 150 128 320 141.8 150 150 130 324
None - - - 25.2 30 30 27 155 26.2 30 30 28 158
11746 16.5 1 19.8 30.6 35 35 28 155 31.9 35 35 29 158
12846 27.8 1 33.4 47.6 50 50 44 155 48.9 50 50 45 158
13346 33 1 39.7 55.5 60 60 51 155 56.8 60 60 52 158
460-3-60 7.8 52 12 7.8 52 12 2.9 4.7 0.5
14246 41.7 2 50.2 68.6 70 70 63 155 69.9 70 70 64 158
None - - - 19.3 20 25 21 129 20.1 25 25 22 131
11758 17 1 16.4 25.9 30 30 24 129 26.9 30 30 25 131
12 (10)
575-3-60 5.7 38.9 9 5.7 38.9 9 2.2 4.3 0.4
13458 34 1 32.7 46.3 50 50 43 129 47.3 50 50 43 131
1 Minimum Circuit Ampacity.
2 Dual Element, Time Delay Type.
3 HACR type per NEC.
4 Non-fused Disconnect. Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field
installed electric heat kits may exceed the factory installed disconnect amperage rating.