Assembly, installation and operating instructions
78
12.2 KaController parameter list
Para-
meter
Function Standard Min. Max. Unit Comment
t001 Serial address 1 0 207 -
Address in Mod-
bus network
t002
Baud rate
0 = Baud rate 4800
1 = Baud rate 9600
2 = Baud rate 19200
2 0 2 -
t003
Background lighting function
0 = Slow fade in, fast fade out
1 = Slow fade in, slow fade out
2 = Fast fade in, fast fade out
0 0 2 -
t004 Strong background lighting 4 0 5 -
t005 Sensor calibration of KaController sensor 0 60 60 °C
t006 LCD display contrast 15 0 15 -
t007
BEEP setting
0 = BEEP ON
1 = BEEP OFF
0 0 1 -
t008 Password for KaController Parameter menu 11 0 999 -
t009 Minimum settable setpoint temperature 8 0 20 °C
t010 Maximum settable setpoint temperature 35 10 40 °C
t011
Interval of setpoint setting
0 = Automatic setting depending on
PCB (parameterisable, freely programmable)
1 = Increment of 1℃ (parametrisable PCBs)
2 = Increment of 0.5 ℃ (freely programmable PCBs)
0 0 2 -
t012 Date/Time setting: Year 9 0 99 -
t013 Date/Time setting: Month 1 1 12 -
t014 Date/Time setting: Day 1 1 31 -
t015 Date/Time setting: Weekday 1 1 7 -
t016 Date/Time setting: Hour 0 0 23 -
t017 Date/Time setting: Minute 0 0 59 -