Parameter Function Standard Min. Max. Unit Katherm HK
9
Katherm HK
E
10
P112 reserved - - - - - -
P113 reserved - - - - - -
P114 reserved - - - - - -
P115 reserved - - - - - -
P116 reserved - - - - - -
P117 Lock function buttons on the KaController 0 0 7 - 0 0
P118 On delay time 0 0 255 sec 0 0
P119 Off delay time 0 0 255 sec 0 0
P120 reserved - - - - - -
P121 reserved - - - - - -
P122 Relative fan speed increase via contact 2 0 5 - 2 2
P123 Maximum valve running time 150 0 255 sec 150 150
P124
Minimum P + I output variation for valve movement
(0 to 10)
5 0 100 % 5 5
P125 reserved - - - - - -
P126 Operating weeks 0 0 255 week 0 0
P127
Information on operating weeks reached (filter mes-
sage)
0 52 255 week 0 0
P128 Reset operating week counter 0 0 1 - 0 0
P129
Fan speed limiter activation in certain operating
modes
0 0 1 - 0 0
P130 Absolute fan speed increase via contact 2 0 5 - 2 2
P131 External ventilation, delay time 0 0 255 min 0 0
P132 Operating level, master password 22 0 255 - 22 22
P133
Hysteresis for outside temperature to switch
between heating / fan mode
0 0 255 K/10 0 0
P134
Threshold for outside temperature to switch
between heating / fan mode
0 0 50 °C 0 0
P135 Activate virtual sensor 0 0 1 - 0 0
P136 Activate external ventilation 0 0 2 - 0 0
Tab.20: Parameter key, standard revision 1.024 from 01.05.2018