CP-Parameter
dulation is switched off!
CP.29 Analog output 1 / Function
CP.29 denes the function of analog output 1.
Value Function Scaling factor
0…100 % (0…±100 %)
0 Absolute actual frequency CP.3 0…100 Hz
1 absolute set frequency CP.2 0…100 Hz
2 actual frequency CP.3 0…±100 Hz
3 set frequency CP. 2 0…±100 Hz
4 output voltage CP.9 0…500 V
5 DC link voltage CP.7 0…1000 V
6 apparent current CP.4 0…2 • rated current
7 active current ru.17 0…2 • ±rated current
8…10 only application mode
11 absolute active current ru.17 0…2 • rated current
12 power stage temperature ru.38 0…100 °C
13 motor temperature ru.46 0…100 °C
14…18 only application mode
19 ramp output frequency ru.2 0…±100 Hz
20 absolute ramp output frequency ru.2 0…100 Hz
CP.31 Relay output 1 / function (terminals X2A.24...26)
CP.32 Relay output 2 / function (terminals X2A.27...29)
The switching level of CP.31 is pre-set to 100,00.
The switching level of CP.32 is adjusted by CP.33!
Va-
lue
Function
0 No function (generally off)
1 Generally on
2 Run signal; also by DC-braking
3 Ready signal (no error)
4 Fault relay
5 Fault relay (without auto-reset)
6 Warning or error message at abnormal stopping
7 Overload pre-warning
8 Overtemperature alert signal power stage
9 External Overtemperature alert signal motor
11 Overtemperature alert signal interior OHI
12 Cable breakage 4...20 mA on analog input 1
14 max. constant current (Stall, CP.25) exceeded
15 max. ramp current (LA-Stop, CP.24) exceeded
16 DC-braking active
20 Actual value = set value (CP.3 = Fcon; rcon; not at noP, LS, error, SSF)
21 Accelerate (CP.3=FAcc, rAcc, LAS)
22 Decelerate (CP.3 = FdEc, rdEc, LdS)
23 Real direction of rotation = set direction of rotation
24 Utilization (CP.6) > switching level

Table of Contents

Other manuals for KEB COMBIVERT F5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F5 Series and is the answer not in the manual?

KEB COMBIVERT F5 Series Specifications

General IconGeneral
Control MethodVector Control, V/f Control
Protection ClassIP20
Protection FeaturesOvercurrent, overvoltage, undervoltage, short circuit, overtemperature
Communication InterfacesCAN, PROFIBUS, Modbus RTU
Cooling MethodFan Cooled
Relative HumidityUp to 95% (non-condensing)

Related product manuals