26
The source rotation setting and the mode of evaluating the rotation setting is defined
with this parameter (Enter-Parameter). With CP.34 one does not modify the rotation
source of the fixed frequencies (CP.19... 21).
CP.34 Source of rotation direction
Value Direction of rotation
0/1 Only application mode
2 Setting by way of terminal strip forward/reverse; negative set values are set to
zero (factory setting).
3 Setting by way of terminal strip forward/reverse; the sign of the set point values
have no effect on direction of rotation.
4 Setting by way of terminal strip run/stop (X2A.14) and forward/reverse (X2A.15);
negative values are set to zero
5 Setting by way of terminal strip run/stop (X2A.14) and forward/reverse (X2A.15);
the sign of the set point values have no effect on direction of rotation.
6 Set value dependent, positive value = clockwise rotation; negative value-
counterclockwise rotation; Status "Low speed" (LS) if no terminal For or Rev is
active
7 Set value dependent, positive value = clockwise rotation; negative value =
counter clockwise rotation clockwise rotation is indicated if set value is "0"
8/9 Only application mode
CP.35 AN1 Set value selection
The set value input 1 (AN1) at the F5-GENERAL control can be triggered by various
signal levels. In order to correctly evaluate the signal, this parameter must be adapted
to the signal source. At the F5-BASIC control in A or B housing the signal source may
not be re-adjusted.
Value Set value signal
0 0...±10 V DC / Ri = 56 kOhm
1 0...+20 mA DC / Ri = 250 Ohm
2 4...20 mA DC / Ri = 250 Ohm

Other manuals for KEB COMBIVERT F5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F5 and is the answer not in the manual?

KEB COMBIVERT F5 Specifications

General IconGeneral
CategoryDC Drives
Enclosure RatingIP20
Control ModeVector Control, V/f Control
ProtectionOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short circuit
Fieldbus CommunicationPROFIBUS, CANopen
Communication InterfacesRS-485
Input Voltage380-480V AC
Cooling MethodForced air cooling (fan)

Related product manuals