4.3 Battery Monitor Settings
2022
13
Battery Type
Lithium or Custom, whichever lets you set the recom-
mended settings
Battery Voltage - Nominal 12 V
Bulk Termination Voltage (if applicable) 13.9 V
Bulk Voltage 14.1 V
Charge Cycle 3 stage
Equalization Disabled
Float Voltage (set below the resting voltage of the bat-
tery bank)
≈13.4 V or lower. Low enough to not trigger oat when
the battery "relaxes" after charging stops.
Max Float Current 10 A
Maximum Charge Rate - 1200 80 A, C/1.25
Maximum Charge Rate - 2400 150 A, C/1.3
Maximum Charge Rate - 3600 200 A, C/1.5
Recharge Volts (≈80% DoD)
Just above your inverter/charger recharge/rebulk volts
so it starts charging from the sun before the inverter
starts charging from the grid or generator.
Setting
Values:
Volts are per battery in a single string.
Amps are per string in parallel
1200 Battery Capacity 1200 Wh, 100 Ah
1200 C-Rating C/1.25
2400 Battery Capacity 2400 Wh, 200 Ah
2400 C-Rating C/1.3
3600 Battery Capacity 3600 Wh, 300 Ah
3600 C-Rating C/1.5
Battery Eciency 94.50%