7.1.3 2400 HLX+
2022
27
Specication Value
Heater 120 W
Internal Resistance ≤20mΩ
Maximum Continuous Charge Current 150 A
Maximum Continuous Discharge Current 150 A
Overcharge Protection Release Method Discharge below ≈14.4 ±0.2 V (3.60±0.05 V / cell)
Overcharge Protection Trigger Voltage ≈15 ±0.12 V (3.75±0.03 V / cell)
Over-discharge Protection Release Method Charge above 11.2V ±0.4 V (2.80±0.10 V / cell)
Over-discharge Protection Trigger Voltage ≈10.2 ±0.2 V (2.50±0.05 V / cell)
Overcurrent Protection - Time delay until high charge
current triggers protection @ 210±5 A
≈25 Seconds
Overcurrent Protection - Time delay until high discharge
triggers protection @ 210±5 A
≈20 Seconds
Overcurrent Protection - Time delay until high discharge
triggers protection @ 400±20 A
≈3.5 Seconds
Overcurrent Protection (Charging) Release Method
Discharge battery for immediate release. Wait 1 minute
for auto-release.
Overcurrent Protection (Discharging) Release Method
Charge battery for immediate release. Wait 1 minute for
auto-release.
Peak or Surge Discharge Current 500 A, less than 3 second
Rated Capacity 200 Ah
Recommended Charge Current ≤100 A