4. - Operation
It is very important that your battery chargers (solar charge controller, inverter/charger or AC) can
be set to settings appropriate for the HLX+. If it cannot, please contact KiloVault Technical Support
for guidance. Adjust your settings as necessary until your system performance best fits your power
use patterns and needs.
Also, some chargers just have settings for broad battery types like; flooded, gel, agm or lithi-
um. Before using these chargers on your battery, please contact KiloVault technical support for
guidance.
Note: If you cannot find a specific setting, remember to check the settings for guidance. Also,
please don’t hesitate to contact KiloVault technical support for help.
4.1 Inverter/Charger Settings
2022
11
Setting
Values:
Volts are per HLX+ in a single string.
Amps are per parallel string.
1200 - Battery Capacity 1200 Wh, 100 Ah
2400 - Battery Capacity 2400 Wh, 150 Ah
3600 - Battery Capacity 3600 Wh, 300 Ah
1200 - Max Charge Current 80 A
2400 - Max Charge Current 150 A
3600 - Max Charge Current 200 A
Absorb End Amps 2 A
Absorb Time (some controllers do not allow a selection
under 6 minutes, please contact KiloVault for additional
information)
2 minutes or less
Absorb Voltage 14.1 V
Battery Temperature Compensation 0 mV/°C
Battery Type
Lithium or Custom, whichever lets you set the recom-
mended settings
Bulk Voltage 14.1 V
Charge Cycle 2 stage no oat
Default Battery Temperature Warm