Chapter 6 List of Parameters
56
code
Name Descriptions Unit
Factory
setting
Modif
Setting
range
A1.19
Selection of power outage
restarting mode
0: Current finding mode
(Only valid in V/F control; Otherwise set
to 0, starting with vector tracking)
1: Vector tracking mode
2: Depend on the parameter A1.00
1 0 X 0 2
Group A2.Frequency setting
A2.00 Auxiliary reference
frequency selector
0: No auxiliary reference frequency
1: AI1
2: AI2
3: Keyboard potentiometer
4: Set by DI (PULSE)terminal
5: output by PID process
1 0 O 0 5
A2.01 Main and auxiliary
reference frequency
calculation
0: +
1: -
2: MAX
(Main reference, Auxiliary reference)
3: MIN
(Main reference, Auxiliary reference)
1 0 O 0 3
A2.02 UP/DN rate 0.01 99.99Hz/s 0.01 1.00 O 1 9999
A2.03 UP/DN regulating control :
0: Save reference frequency upon
power outage
1: Not save reference frequency
upon power outage.
:
0: Hold reference frequency at stop
1: Clear reference frequency at stop
:
0: UP/DN integral time valid
1: UP/DN speed value
1 000 O 0 111H
A2.04 Jog operatingfrequency 0.10 50.00Hz 0.01Hz 5.00 O 10 5000
A2.05 Interval of Jog operation 0.0 100.0s 0.1s 0.0 O 0 1000
A2.06 Skip frequency 1 0.00 300.00Hz 0.01Hz 0.00 X 0 30000
A2.07 Range of skip frequency1 0.00 30.00Hz 0.01Hz 0.00 X 0 3000
A2.08 Skip frequency 2 0.00 300.00Hz 0.01Hz 0.00 X 0 30000
A2.09 Range of skip frequency 0.00 30.00Hz 0.01Hz 0.00 X 0 3000
A2.10 Skip frequency 3 0.00 300.00Hz 0.01Hz 0.00 X 0 30000
A2.11 Range of skip frequency3 0.00 30.00Hz 0.01Hz 0.00 X 0 3000
Group A3.Setting curve
A3.00 Reference frequency
curve selection
0: Curve 1
1: Curve 2
2: Curve 3
3: Curve 4
1 0000 O 0 3333H