Chapter 6 List of Parameters
55
code
Name Descriptions Unit
Factory
setting
Modif
Setting
range
Group A1.Start and stop parameters
A1.00 Starting mode 0: Start from the starting frequency
1: Brake first and then start
2: Start on the fly(including direction
judgement), start at starting frequency
3: Current search type speed tracking
starting (only valid in V/F control)
1 0 X 0 2
A1.01 Starting frequency 0.00 60.00Hz 0.01Hz 0.00Hz O 0 6000
A1.02 Holding time of starting
frequency
0.00 10.00s 0.01s 0.00s O 0 1000
A1.03 DC injection braking
current at start
0.0% current 0.1% 0.0% O 0 1000
A1.04 DC injection braking time
at start
0.00(No action)
0.01 30.00s
0.01s 0.00s O 0 3000
A1.05 Stopping mode 0: Dec-to-stop
1: Coast-to-stop
2: Dec-to-stop+DC injection braking
1 0 X 0 2
A1.06
DC injection braking initial
frequency at stop
0.00 60.00Hz 0.01Hz 0.00Hz O 0 6000
A1.07 Injection braking
waiting time at stop
0.00 10.00s 0.01s 0.00s O 0 1000
A1.08 DC injection braking
current at stop
0.0% 0.1% 0.0% O 0 1000
A1.09 DC injection braking time
at stop
0.0(No action)
0.01 30.00s
0.01s 0.00s O 0 3000
A1.10 Restart after power failure
0: Disable
1: Enable
1 0 X 0 1
A1.11
Delay time for restart after
power
0.0 10.0s 0.1s 0.0s O 0 100
A1.12 Anti-reverse running
function
0: Disabled
1: Enabled
(It will operate at zero frequency when
input a reverse command)
1 0 X 0 1
A1.13 Delay time of run
reverse/forward
0.00 360.00s 0.01s 0.00s O 0 36000
A1.14
Switch mode of run reverse
/ forward(Reserved)
0: Switch when pass 0Hz
1: Switch when pass starting frequency
1 0 X 0 1
A1.15 Stopping speed 0.00 150.00Hz 0.01Hz 0.10Hz X 0 15000
A1.16 Action voltage of braking
unit
650 750V 1 720 X 650 750
A1.17 Dynamic braking 0: Disable
1: Enable
1 0 X 0 1
A1.18 Ratio of working time of
working time
0.0 100.0% 0.1% 80.0% O 0 1000