Chapter 6 List of Parameters
78
code
Name Descriptions Unit
Factory
setting
Modif
Setting
range
C1.24 Preset close-loop
reference 6
-10.00V 10.00V 0.01V 0.00V O 0 2000
C1.25 Preset close-loop
reference 7
-10.00V 10.00V 0.01V 0.00V O 0 2000
C1.26 Preset close-loop
reference 8
-10.00V 10.00V 0.01V 0.00V O 0 2000
C1.27 Preset close-loop
reference 9
-10.00V 10.00V 0.01V 0.00V O 0 2000
C1.28 Preset close-loop
reference 10
-10.00V 10.00V 0.01V 0.00V O 0 2000
C1.29 Preset close-loop
reference 11
-10.00V 10.00V 0.01V 0.00V O 0 2000
C1.30 Preset close-loop
reference 12
-10.00V 10.00V 0.01V 0.00V O 0 2000
C1.31 Preset close-loop
reference 13
-10.00V 10.00V 0.01V 0.00V O 0 2000
C1.32 Preset close-loop
reference 14
-10.00V 10.00V 0.01V 0.00V O 0 2000
C1.33 Preset close-loop
reference 15
-10.00V 10.00V 0.01V 0.00V O 0 2000
C1.34 Close-loop output
reversal selection
0: The close-loop output is negative,
the drive will operate at zero frequency.
1: The close-loop output is negative,
and the drive operate reverse.
1 0 O 0 1
C1.35 Sleep function selection 0: Disable
1: Enable.
1 0 O 0 1
C1.36 Sleep level 0.0 100.0% 0.1% 50.0% O 0 1000
C1.37 Sleep latency 0.0 6000.0s 0.1s 30.0s O 0 6000
C1.38 Wake-up level 0.0 100.0% 0.1% 50.0% O 0 1000
C2.Simple PLC
C2.00 Simple PLC
operationmode selector
: PLC operation
mode
0: No function
1: Stop after single cycle
2: Keep final states after single
cycle
3: Continuous cycle
: Start mode
0: Start from first step
1: Start from the step before stop
alarm).
2: Start from the step and frequency
before stop (or alarm)
: Storage after
power off
1
0000
X 0 1123H