Chapter 6 List of Parameters
82
Function
code
Name Descriptions Unit
Factory
setting
Modif
.
Setting
range
d0.30 Total conduction time 0 65535 hours 1 hours
0 * 0 65535
d0.31 Total operating time 0 65535 hours 1 hours
0 * 0 65535
d0.32 0 65535 hours 1 hours
0 * 0 65535
d0.33 ASR controller output -300.0 300.0%
0.1% 0.0% * 0 6000
d0.34 Reference torque -300.0 300.0%
0.1% 0.0% * 0 6000
d0.35 Zero offset of AI1 0 65535 1 0 * 0 65535
d0.36 Zero offset of AI2 0 65535 1 0 * 0 65535
d0.37 Zero offset of Keyboard
potentiometer
0 65535 1 0 * 0 65535
d0.38
d0.39
Reserved - - - - -
d0.40 Operating counter value 0 65535 1 0 * 0 65535
d0.41
d0.45
Reserved - - - - -
Group d1.Fault record
d1.00 Fault record 1 0: No fault records
1: Hardware over current during
acceleration.
2: Hardware over current during
deceleration.
3: Hardware over current during
running in constant speed.
4: Hardware over voltage during
acceleration.
5: Hardware over voltage during
deceleration.
6: Hardware over voltage during
running in constant speed.
7: Input voltage is too high
8: Input phase loss (E008)
9: Output phase failure (E009)
10: 22kw and above models.IGBT
module is detected voltage drop too
large. (IGBT module protection)
11:
12: heat.
13: Running current is larger than VFD
rated current for long time.
14:
Running current is larger than motor
rated current for long time.
15: External device fault.
1 0 * 0 50