AutoStart On The unit has detected an Autostart signal when not in auto mode,indicating
the engine needs to be started in Auto mode.
Scheduler On The unit has detected that a scheduled run is due when not in auto
mode,indicating the engine needs to be started in Auto mode.
Low Oil Pressure The Oil Pressure has dropped below the Oil Pressure Warning set point
while the engine is running. The Oil Pressure Icon is lit.
High Engine Temp Engine temperature has exceeded the high temperature warning set point.
The temperature icon is lit.
High Canopy Canopy Temperature has exceeded the high canopy temperature setpoint
Temperature after the Temperature monitoring delay has expired.
Low Fuel Level Fuel level is less than the warning set point.
Fuel Level Flt The unit has detected that the fuel sender is open circuit. This is only a
warning, and will not shut down the engine
Can Temp Flt The unit has detected that the canopy temperature sender is open circuit
or has shorted to common.
No Speed Signal A speed signal could not be detected after the engine had started
Maintenance The time since the last maintenance has exceeded the maintenance
time. The alarm output is not activated for this warning. The maintnenace
Output (if configured) is activated. The warning is cleared by pressing
and holding the button for 30 seconds. If the engine maintenance is
carried out prior to the timer expiring, pressing the button for 60 seconds
will reset the timer.
User Message The user has detected a warning associated with the user analog input
4.11.12 Communications
The unit is fitted with a fully functional communications port, which communicates using Modbus ASCII
protocol. This port may be plugged into RS232 or RS485 communication adaptors and through these to
a modem or a multidrop network.
4.11.13 Alarm Dial Out
The unit can be configured to dial out to an KG PowerLink application when an alarm is activated.
Before the dial out can function, the unit must have some Phone Numbers setup by either KG PowerLink
or KG PowerConfig applications. These values cannot be edited locally via the menu.
Alarm dial out requires the use of an RS232 interface connected to a modem.
4.11.13 Specifications
Feature Specification
Overall Dimensions 110 x 100 x 60mm
Mounting Hole 96 x 96 mm
IP rating IP66 front, IP55 rear
Supply Voltage 6 V to 36V DC
Nominal 12V or 24V Automotive
Supply Current Standby < 7mA
Running 100mA TBA