60
Speed Input Sensitivity 0.5 - 350 Volts Pk
Input reference 0 volts common
Speed Frequency Range 10Hz – 20KHz
Displayed speed range 0 – 9999 RPM
Engine Hours 0 – 99999.9 Hours
Oil pressure sensor type Switch: close on fault, open on fault
Resistive 10 to 180 Ohms (VDO/Datcon)
Resistive 0 to 90 Ohms (Pricol/Datcon)
User Curve
Oil Pressure range 500, 750, 1000 KPa
Engine Temperature sensor type Switch: close on fault, open on fault
Resistive (NTC)
Engine Temperature range 120ºC, 200ºC, User Curve
Canopy Temperature sensor type Switch: close on fault, open on fault
Resistive (NTC)
Canopy Temperature range KG907 supplied unit, User Curve
Fuel Level Sensor type Switch close to Fault, open on fault.
Resistive 0 to 90 Ohms
Resistive 10 to 180 Ohms
User Curve
Battery Volts measurement 6 to 40 Volts
Outputs 3 Amp Contact (24 volt resistive) switching to common
HET, LOP, Fail to Start, Low 3 Amp Contact (24 volt resistive) switching to isolated common
Fuel outputs
Con A, Con B NO/NC Isolated 3 Amp with 230V rating
Set-up and Adjustment All features may be adjusted using set-up buttons and LCD menu.
Terminations Amp DUAC / Molex Mini Fit JNR