EasyManua.ls Logo

KMC Controls CSC-3000 Series - Troubleshooting; Maintenance; Important Notices

KMC Controls CSC-3000 Series
15 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CSC-3000 Series Pneumatic VAV Reset Volume Controllers 7 Applications Guide, Rev G
Troubleshooting
NOTE: The controller should be set according
to the specications found on the
manufacturers label on the VAV box.
NOTE: The CSC-3000 series are position sensitive.
Be sure to mount the controller with
the correct orientation. See Mounting on
page 2. If the controller is calibrated in a
position other than the nal mounting
position, the calibration (minimum and
maximum ow limits) will be o.
NOTE: Thesecontrollersaretypicallyusedon
single-ductapplicationsbutmaybe
foundindual-ductapplications.(See,for
example,Dual Duct on page 13andDual
Duct, Constant Volume on page 14
.)When
workingondual-ductapplicationsitmay
benecessarytoworkononeductatatime.
Troubleshootingissuestoconsiderinclude:
• Isthereanadequatemainair(M)supply?
• Isthereadequateupstreamsystem(duct)air?
• Istheapplicationcorrectandpipedcorrectly?
SeeConnections on page 3,Determining the Type
of Reset on page 4
,andApplications on page 10.
•
Isthedamperaction(NC/NO)setcorrectly?Do
thedampersandcontrollersactionmatch?See
Damper Action on page 4.
•
Isthedamperbinding?Willtheactuatordrive
thedamperfullopentofullclose?(Sucient
mainairisrequiredtoprovidetheactuatorwith
enoughforcetooperatethedamper/linkage.)Is
theactuatorleaking?(Evensmallleakscancause
theactuatortonotstroke.Youcantestforleaks
withasqueezebulbtoensuretherearenoleaks
attheactuatordiaphragmorings.)
• Doesthethermostatsendanadequatesignalto
thecontroller?
• AreLOSTATandHISTATsetcorrectlyforthe
thermostataction?Whencycled,canthecontrol-
lerrepeattheLOSTATandHISTATseings?If
theLOSTATorHISTATmustbesetfor“0”wc,
seethenotesaboutzero minimuminDIRECT
Reset Minimum and Maximum on page 4
orRE-
VERSE Reset Minimum and Maximum on page 5.
Maintenance
Noroutinemaintenanceisrequired.Eachcompo-
nentisdesignedandmanufacturedforreliability
andperformance.Carefulinstallationandusewill
ensurelong-termdependability.
CAUTION
Pneumatic devices must be supplied with clean,
dry control air. Any other medium (e.g., oil
or moisture contamination) will result in the
device’s eventual failure.
• Istheairowpickupproperlyplaced,anddoesit
sendagooddierentialpressuretothecontrol-
ler?(SeeConnections on page 3.)Istheairow
sensordirtyordefective?(Disconnectthesensor
fromthecontrollerbeforeaemptingtoblowthe
sensorclean!)
• Areresetstartandresetspansetcorrectly?See
Reset Start Point on page 6andReset Span on
page 6.
Important Notices
TheKMClogoisaregisteredtrademarkofKMC
Controls,Inc.Allrightsreserved.Nopartofthis
publicationmaybereproduced,transmied,tran-
scribed,storedinaretrievalsystem,ortranslated
intoanylanguageinanyformbyanymeanswith-
outthewrienpermissionofKMCControls,Inc.
Thematerialinthisdocumentisforinformation
purposesonly.The contents and the product it de-
scribes are subject to change without notice.KMC
Controls,Inc.makesnorepresentationsorwarran-
tieswithrespecttothisdocument.Innoeventshall
KMCControls,Inc.beliableforanydamages,direct
orincidental,arisingoutoforrelatedtotheuseof
thisdocument.

Related product manuals