TP-7203 4/23 45
Section 5. Prestart Check and Test
5.1 Prestart Installation Check
Review the entire installation sections. Inspect all wiring and connections to verify that the generator set is ready for operation.
Check all items in the following Prestart Checklist.
Prestart Checklist
Air Cleaner. Check that a clean air cleaner element is installed to prevent unfiltered air from entering the engine. See the
generator set operation manual for instructions.
Air Inlets. Check for clean and unobstructed air inlets.
Battery. Check for tight battery connections. Consult the battery manufacturer’s instructions regarding battery care and
maintenance.
Coolant Level. Check the coolant level as described in the Cooling system section.
Note:
Block Heater Damage. The block heater will fail if the energized heater element is not immersed in coolant. Fill the cooling
system before turning on the block heater. Run the engine until it is warm, and refill the radiator to purge the air from the system
before energizing the block heater.
Enclosure. Check that all enclosure panels and internal baffling are in place.
Exhaust System. Check for exhaust leaks and blockages. Check the muffler condition.
Inspect the exhaust system components for cracks, leaks, and corrosion. Check for tight exhaust system connections.
Check for corroded or broken metal parts and replace them as needed.
Check that the exhaust outlet is unobstructed.
Oil Level. Maintain the oil level at or near, not over, the full mark on the dipstick.
Operating Area. Check for obstructions that could block the flow of cooling air. Keep the air intake area clean. Do not leave
rags, tools, or debris on or near the generator set.