164 TP-6694 9/20
Description
Controller
Display
Message
Write
Access
Display
SiteTech
GenSet
Mode
Always
Running
Stopped
Range
Setting
Default
Selection
Time
Delay
Range
(sec.)
Default
Time
Delay
(sec.)
Programmer-
Defined
Settings
Charger Temperature
Compensation Slope
(mV/°C)
S
A
-400
(12 V)
-800
(24 V)
-30
(12 V)
-60
(24 V)
Adjustable with
Charger
Custom Profile
enabled.
Charger Voltage
Absorption (V)
S
A
1315
(12 V)**
2630
(24 V)**
14.25
(12 V)
28.5
(24 V)
Adjustable with
Charger
Custom Profile
enabled.
Charger Voltage Bulk
(V)
S
A
1315
(12 V)**
2630
(24 V)**
14.25
(12 V)
28.5
(24 V)
Adjustable with
Charger
Custom Profile
enabled.
Charger Voltage
Equalize (V)
Note:
Equalize is only
available with
FLA/VRLA topology
selected.
S
A
1416
(12 V)
2832
(24 V)
Adjustable with
Charger
Custom Profile
enabled.
Charger Voltage Float
(V)
S
A
1314
(12 V)**
2628
(24 V)**
13.25
(12 V)
26.5
(24 V)
Adjustable with
Charger
Custom Profile
enabled.
Current transformer
ratio ]
S
S
1-
1200
ECM power
S
S
0-1
0
0-600
300
Engine cooldown delay
S
A
10-30
15
Engine (cyclic) crank on
S
A
1-60
15
Engine (cyclic) crank
pause
S
A
0-300
0
Engine ECM start delay
S
A
0-60
60
Engine idle duration
S
A
Engine no. of (cyclic)
crank cycles
S
S
1-6
3
Engine restart delay
S
A
1-10
10
Engine start aid delay
S
A
0-10
0
Engine start delay
S
A
0-300
0
Equalize Current Limit
(A)
Note:
Equalize is only
available with
FLA/VRLA topology
selected.
S
A
15
Adjustable with
Charger
Custom Profile
enabled.
Forced Charge Cycle
Reset
S
A
Active
Inactive
Inactive
Output Enable
Reduced Out
S
A
Fixed
Active
Voltage regulator gain
S
R
1-255
128
Voltage regulator
stability adjust
S
R
1-255
128