TP-6928 1/14 25Section 2 OnCue Plus Operation
Status Screen Item Indicates Notes
Name Name of generator that you are
monitoring
Select the generator from the list on the left side of the screen.
(Click on the arrow symbol to reveal the list.)
Generator status
message
The status of the generator that
you have selected
Examples of status messages are “Generator Running” and
“Standby.” If a fault condition is indicated, check the Event
History view or the controller display to identify the fault.
Time Time of the last update The frequency of updates can be changed through the Settings
screen.
GEN Symbol Generator Status Green when active, gray when not available.
Power Line Symbol Utility power status Green when active, gray when not available.
Home Symbol and
home status message
Home does or does not have
power
Symbol is green when the home has power from either the
generator or utility.
Total Power Power being supplied to the
home, in kW (LCM required)
Gives an indication of how much power is being used, allowing
power management through OnCue Plus.
Battery Voltage Generator engine starting battery
voltage
Typically 12--15 volts DC. A voltage below 12.5 VDC will
trigger a low battery voltage warning, indicating that the battery
should be charged or replaced. A voltage less than 11 volts
DC will be displayed in red.
Figure 2-9 Status Screen Displays