APPENDIX C. Troubleshooting
C.1 Connections
If the motor does not rotate check that the connections are correct. Refer to the circuit
diagrams and maintenance instruction AS-11.65.020.
C.2 Drive fault codes
Check the connection of connectors XSR1
(safety relay input) and
XM1 (MLB
Interface) on HCB board.
Refer to the circuit diagrams.
If you have to change the connection of the
connector XSR1 (safety relay input) or XM1
(main contactor supervision), switch the
power off.
The new connection will be valid after
power up.
One example of the connections:
Safety relay connection is not used.
Main contactor (A) is supervised.
XSR1 is overconnected. Set the value of
parameter
(6_38) to 0, 1, 2, or 3.
Fault Symptoms of fault Action
Drive faults
0101
Drive stop
Emergency stop or
Error detected by the drive
diagnostics.
See other fault codes.
0102
Motor overcurrent.
Emergency stop.
Prevents new drive before
the fault is corrected.
• Check the drive parameters.
• Check the current scaling.
• Check the mechanical brake.
0103
Damaged Braking resistor
or electrical circuits.
Emergency stop • Check the circuits of the
braking resistors.
• Check condition and
connection of the braking
resistors.