EasyManua.ls Logo

KROHNE OPTIMASS Series - Replacing the Front End or Back End Electronics

KROHNE OPTIMASS Series
109 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation and Operating Instructions OPTIMASS
96
Zero Problems
Perform auto zero, observe the displayed value, it should be stable and lower than +/- 0.5%
If the result is bad:
Stop flow, set 3.1.1 Low flow cut off to 0, 3.1.3 Flow Mode to “+/-”, perform auto zero,
and totalise over 2 minutes. Compare totalised flow to specified zero stability.
For best process results, zero setting should be performed on process fluid at process temperature.
High Zero’s can be caused by: Leaking valves, Air/Gas inclusions, Coating on tube.
Driver or Sensor Coil Fault
Typical inductance and resistance values:
OPTIMASS 7000
Inductance (mH) Resistance (Ohm) OPTIMASS
7000
Driver Sensor A/B Driver Sensor A/B
06/10 5.30 (4.32) 17.32 (10.36) 37 - 42 147 - 152
15 11.7 (8.9) 17.32 (10.36) 47 - 51 147 - 152
25/40 13.1 (11.3) 17.32 (10.36) 40 - 41 147 - 152
50/80 23.5 (12.9) 17.32 (10.36) 49 - 51 147 - 152
The above data are provided as a rough guide only.
Damaged magnet coil assembly: Inductance values in brackets.
Driver = Black and Grey.
Sensor A = White and Yellow. Sensor B = Green and Purple.
RTD = Red and Blue (530...550 ) at ambient temperature
Tube strain = Red and Brown:
OPTIMASS 7000 – 06 600 - 800 at ambient
OPTIMASS 7000 – 10...80 420 - 560 at ambient
IC strain = Brown and Orange
OPTIMASS 7000 – 06...10 225 - 275 at ambient
OPTIMASS 7000 – 15...80 Not fitted
Resistance values outside these values could indicate a circuit failuire. Meter may be in start-up or
have measuring errors.
All circuit should be isolated from ground (meter case) and each other: >20M. If circuits are shorting
to ground, meter may be in start-up.
Caution:
Fluid may be in secondary containment – possible tube failure. Depressurise and safely remove from line
as soon as possible.
OPTIMASS 3000 (7100)
Inductance (mH) Resistance (Ohm)
OPTIMASS
3000 (7100)
Driver Sensor A/B Driver Sensor A/B
01 1.2 (1.2) 7.2 (7.2)* 54 – 60 105 - 110
03/04 2.6 (8.9) 10.5 (10.36) 43 – 50 132 - 138
The above data are provided as a rough guide only.
Damaged magnet coil assembly: Inductance values in brackets.
Driver = Purple/Black and Orange/Grey.
Sensor A = White and Yellow. Sensor B = Green and Yellow.
RTD = Red and Blue (530...550 ) at ambient temperature
Resistance values outside these values could indicate a circuit failure. Meter may be in start-up or have
measuring errors.
All circuit should be isolated from ground (meter case) and each other: >20M. If circuits are shorting
to ground, meter may be in start-up.
Caution:
Fluid may be in secondary containment – possible tube failure. Depressurise and safely remove from line
as soon as possible.

Table of Contents

Related product manuals