lares 4.0 Programming manual
91 R30024.130en
3.9.13 Notifications
This page links the notifications (calls, SMS, etc.) with various events.
To program the "Notifications" the following parameters must be configured:
Type It identifies the group generating notification (i.e. zone, partition, output, etc.).
Subtype This is the event related to the previous parameter (i.e. Type: Zone -> Subtype:
zone alarm). You can make a multiple choice with up to 15 items.
After having configured the previously described two parameters, click on
( ). At this point it is necessary to set two other parameters:
• Entities: enter the zone, the partition, the device, the user, etc., that
generates the notification.
• Contact list: enter a previously programmed contact list, which will receive
calls, text messages, e-mails, and the contact ID message
The notification types are listed below the “Subtypes”.
Type: Zone
The subtypes available are:
• Alarm: send a message when the zone generates an alarm.
• Restore: send a message when the zone is restored after an alarm.
• Pre-alarm: send a message when the zone generates a pre-alarm.
• Tamper: send a message when the zone generates a tamper alarm.
• Tamper restore: send a message when a tamper is restored.
• Bypass: send a message when the zone is excluded.
• Unbypass: send a message when the zone is included.
• Mask: send a message when the detector generates a masking alarm.
• Mask restore: send a message when the detector's masking condition is
restored.
• Real time - Alarm: send a message when the zone is alarmed, even with the
partition switched off.
• Real time - Restore: send a message when the previous condition will be
restored.