57
Bypass Freq Tracking Range: When the difference between the bypass input
frequency and the rated frequency is greater than this value, the system determines
that the bypass frequency is not normal, and that the bypass is unavailable. The
value range is 1%, 2%, 4%, 5%, 10%(default).
Bypass rate tracking rate: Inverter frequency tracking to bypass frequency rate.The
value range is 0.5~2, and is 1 by default.
Power Supply upon bypass Over Temp: Specifies whether to start bypass mode when
overtemperature occurs. The default value is Enable.
Bypass Switches Limit: Cross currents occur during the transfer between bypass mode
and normal mode, which impacts the system. This parameter
specifies the number of transfers between bypass mode and
normal mode within 1 hour, which ensures system security. The
value can be 3 to 10, and is 10 by default.
EPO transfers to bypass: Specifies whether to start bypass mode when EPO occurs.
The default value is Enable.