56
Cabinet shared battery: tow parallel ups use common batter bank. The value can be
set share battery pack or Not shared battery P, not shared battery P by default.
Generator on prohibit charging: UPS disable charge the battery if set the value to
enable when the generator signal is enable.
Bypass Volt Prot Lower Limit: When the difference between the bypass voltage and
the rated voltage exceeds the lower threshold for the bypass voltage, the system
determines that the bypass voltage is abnormal and that the bypass is unavailable. The
value can be –10%, –15%, –20%, –30%, –45%,. The default value is –45%.
Bypass Volt Prot Limit: When the difference between the bypass voltage and the rated
voltage exceeds the upper threshold for the bypass voltage, the system determines that
the bypass voltage is not normal and that the bypass is unavailable.
NOTE:
When the voltage level is 380 V, the value range is 10%, 15%, 20%, and 25% (default).
  When the voltage level is 400 V, the value range is 10%, 15%, and 20% (default).
  When the voltage level is 415 V, the value range is 10% and 15%(default).