55
Chg.cur.limiting coef.: The charging current limit is a multiple of the battery capacity.
The value can be 0.05–0.15, and is 0.1 by default.
Cell float voltage: The float voltage value can be 2.23-2.30 V/cell, and is 2.25 V/cell by
default.
Cell boost voltage: The battery equalized voltage value can be 2.30–2.40 V/cell, and is
2.30 V/cell by default.
Aver charging Duration: boost charge time limit, the value can be 1–999min, and is
240 by default.
EOD Battery Volt: End of discharge voltage. The value can be 1.60~1.90, and is 1.80 by
default.
Float Temp Compen Coeff: modify the voltage of compensation after enable the switch.
the value can be 0.001~0.007/cell, and is 0.003 by default.
Boost Charge Setting: Boost charge disable or enable, and is enable by default.
No Battery Warning: can be no warning when no batter after set disable, and is enable
by default.