Cabinet Paral Redunt Units: Parallel redundancy cabinet number, can modify the
redundancy cabinet number after set work mode to
parallel mode. The value can be 0~5, default value is 0.
Output Freq: Output frequency, The value can be 50Hz or 60Hz.
Output Volt Level: Output voltage level, The value can be 220V, 230V, 240V.
Output Ivn Volt Regu: Inverter voltage regulated, The value can be -5%~0~+5%, step is
0.5%, default value: 0.
Battery Group: Must modify the number to actual configuration, The value can be 1~8,
default value is 1.
Battery number: Must modify the number to actual configuration, The value can be
30~50, default value is 32.
Single Battery Capability: Must modify the value to actual configuration, the value can
be 7~2000.
Boost/Float conversion: boost charge and float charge alternate time, the value can be
0~20.