EasyManua.ls Logo

KVM KVM6000 Series - Page 32

KVM KVM6000 Series
54 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- 30 -
- 31 -
KVM6000
Function Code Table
KVM6000
Function Code Table
current reaching 1
detection value
current reaching 1
detection range
P8-20
P8-21
0Second 1Minute 2Hour
0200.0%
0100.0%
100.0%
5.0%
0814H
0815H
Frequency detection
value (FDT2)
P8-17
50.00Hz
0811H
Detection
range of FDT2
P8-18
0.00Hz
0812H
P8-19
3.0Hz
0813H
Detection range of
frequency
consistent
P8-22
0200.0%
150.0%
0816H
current reaching 2
detection value
P8-23
P8-26
P8-29
Current reaching
2 detection range
Output
overcurrent
threshold
Timing duration
setting
0100.0%
0.0%600.0%
0.06500.0Min
5.0%
5.0%
0.0Min
0817H
081AH
081DH
P8-24
Zero current
detection level
0100.0%
5.0%
0818H
P8-25
Zero current
detection
delay time
0.0%600.0%0.20s
0819H
P8-27
Output
overcurrent
detection delay
0.0%600.0%0.20s
081BH
P8-28
Timing
operation
function
BIT0: Timing function selection
0: Invalid 1: Valid
BIT1: Timing operation time selection
0: P8-29 setting 1: AI1
2: AI2 3: AI3
Analog input range 100% corresponds to P8-28
BIT2: Reserved BIT3: Reserved
0000
081CH
P8-300
081EH
Timer time unit
0: Second 1: Minute 2: Hour
P8-31
0
081FH
Timer set value
0: Second 1: Minute 2: Hour
P8-32
1000
0820HCounter Max
065000
P8-33500
0821H
Counter set value
065000
P8-34
3.10%
0822H
AI1 voltage
protection value
lower limit
0.0P8-35
P8-35
6.80%
0823H
AI1 voltage
protection value
upper limit
P8-35100.0%
P8-36
75.0%
0824H
Module
temperature
reached
0100℃
BIT0Motor overload protection selection
0Invalid 1Valid
BIT1Ground fault duringpower-on
0Invalid 1Valid
BIT2Input phase loss protection selection
0Invalid 1Valid
BIT3Output phase loss protection selection
0Invalid 1Valid
1011
Protection
function
selection 1
P9-000900H
P9 Fault and protection parameters
Function
Code
Parameter Name
Setting Range
Default
Address
BIT0: Output load loss protection selection
0: Invalid 1: Deceleration 2: Ramp to stop
BIT1: Instantaneous power failure action
selection
0: Invalid 1: Valid
BIT2: Continue operation frequency selection
in case of failure
0: Operate at current operation frequency
1: Operate at set frequency
2: Operate at the upper limit frequency
3: Operate at the lower limit frequency
4: Operation at abnormal standby frequency
BIT3: Action selection of fault DO”during
fault automatic reset
0: No action 1: Action
0000
Protection
function
selection 2
P9-010901H
P9-02
Fault auto
reset times
00902H
0: OFF
Automatic reset function is turned off, only
manual reset is allowed.
1-20: ON
This function is on, 1-20 is the number of
times of self recovery after failure (defined
as the maximum number of times of auto reset
after each failure)
P9-03
Time interval of
fault auto reset
0.01s0903H
0.1100.0s
P9-04
1st
fault type
Read-only
0904H
1 -- ERROR_INVERTER UNIT
2 -- ERROR_OC_DURING_ACC
3 -- ERROR_OC_DURING_DEC
4 -- ERROR_OC_AT_CONST_SPEED
5 -- ERROR_OV_DURING_ACC
6 -- ERROR_OV_DURING_DEC
7 -- ERROR_OV_AT_CONST_SPEED
8 -- ERROR_CONTROL POWER SUPPLY
9 -- ERROR_UV
10 -- ERROR_OL_AC DRIVE
11 -- ERROR_OL_MOTOR
12 -- ERROR_LOSE_PHASE_INPUT
13 -- ERROR_LOSE_PHASE_OUTPUT
14 -- ERROR_OH_MODULE